PXU20020 Datasheet, PDF (12/32 Pages) Red Lion Controls. Inc – MODEL PXU - TEMPERATURE/PROCESS CONTROLLERS
7.1 MODULE 1 - Input Parameters (1-IN)
1-INP
P
PARAMETER MENU
CNFP
P
tYPE
INPUT
TYPE
SCAL
TEMP
SCALE
dCPt FLtr
DECIMAL
DIGITAL
RESOLUTION FILTERING
bANd
FILTER
BAND
SHFt
SHIFT/
OFFSET
dSP1
DISPLAY
VALUE 1
dSP2
DISPLAY
VALUE 2
SPLO
SETPOINT
LOW LIMIT
SPHI
SETPOINT
HIGH LIMIT
Programming/model dependent.
CJC
COLD
JUNCTION
USr1
USER
INPUT 1
USr2
USER
INPUT 2
F1In
F1 KEY
FUNCTION
F2In
F2 KEY
FUNCTION
 
 
INPUT TYPE
SELECTION TYPE
K K TC
J J TC
t T TC
E E TC
N N TC
r R TC
S S TC
b B TC
L L TC
U U TC
SELECTION TYPE
tK TXK TC
2 RTD 392
 RTD 385
nI RTD 672
cU Cu 50
Su 0-5 Volt
10u 0-10 Volt
0-20 0-20 mA
4-20 4-20 mA
0.05u 0-50 mV
Select the input type that corresponds to the input sensor.
 
 
TEMPERATURE SCALE
 Fahrenheit
 Celsius
Select either degrees Fahrenheit or Celsius. If changed, check related
parameter values.
* Temperature Input only.
bANd 
1
INPUT FILTER BAND
1 to 100 display units
The filter will adapt to variations in the input signal. When the variation
exceeds the input filter band value, the digital filter disengages and a noise
discrimination filter engages that rejects noise bursts. When the variation
becomes less than the band value, the digital filter engages again. The value of
the band is in display units.
 

SHIFT/OFFSET
 to  display units
This value offsets the controller’s display value by the entered amount. This
is useful in applications in which the sensor does not provide an accurate signal.
DISPLAY VALUE SCALING POINT 1
 

 to 
Enter the first coordinate zero Display Value associated with the lower range
(0V/mA, 4mA) of the input signal, by using the arrow keys.
 

DECIMAL RESOLUTION
 to 0 for temperature inputs
 to 0 for process inputs
Select whole degrees, or tenths of degrees for Temperature display, Setpoint
values, and related parameters. For thermocouple types R, S, and B, only whole
degrees of resolution is available. For process inputs up to three decimal point
resolution is available.
DISPLAY VALUE SCALING POINT 2
   to 
 0
Enter the second coordinate full scale Display Value associated with the
upper range (5V, 10V, etc) of the input signal, by using the arrow keys.
* Process input only.
 
8
DIGITAL FILTERING
 = least to 50 = most
The filter is an adaptive digital filter that discriminates between measurement
noise and actual process changes. The equation for digital filtering is:
Last displayed PV [ n + measured value
PV =
n+1
Where: n = Digital Filtering selection
If the signal is varying greatly due to measurement noise, increase the filter
value. Decrease the filter value for quicker controller response.
 
 -148
SETPOINT LOW LIMIT
 to  input range dependent
The controller has a programmable low setpoint limit value to restrict the
range of the setpoint. Set the limit so that the setpoint value cannot be set below
the safe operating area of the process.
Shaded parameters are programming/model dependent.
12