English
Language : 

VT-UIPM-431-H Datasheet, PDF (1/2 Pages) Red Lion Controls. Inc – Industrial RTU
MICRO-Versa TRAK µlPm™
Sixnet Automation Devices
PRODUCT DATASHEET
VT-UIPM-
MICRIOnd-VuesrtrsiaTl RTAUK uIPmTM
An Installation-ready Interface for Real-time Plant Floor Data
PRODUCT HIGHLIGHTS
 Plant floor interface for Real-time inventory management,
Remote process monitoring, HVAC & energy management,
environmental monitoring, low cost OEM applications
 Ideal for ID tag applications, serial ports link to code readers
 Datalogging and timestamping trending, alarm logging, &
transaction recording
 Stand alone control of remote sites, IEC 61131 ISaGRAF and
also C++ programming via open source Linux
 Limitless multi-user connectivity telephone, Internet, and
wireless telemetry, 10/100 Ethernet plus up to 4 com ports
 Embedded Linux open source software, add applications,
I/O drivers & much more
 An OEM’s dream platform, pre-certified, add your application
PERFORMANCE SPECIFICATIONS
 Industrial PowerPC (32 bit data bus)
 Operating system embedded open-source Linux
 Dynamic memory (RAM) 16 Mbytes for program execution,
dynamic variables, dynamic file system, etc.
 Program memory (Flash) 16 Mbytes for Linux OS, program
storage and file system
 Retained memory (RAM) 512K (battery-backed) for
datalogging and retained variables
 Real-time clock battery-backed for time stamping and other
operations
 Local I/O (on-board) 12 or 14 (see ordering info.)
 I/O Expansion (up to 256) RS485 or Ethernet
 Datalogging support
 IEC 61131 programming, ISaGRAF for ladder logic, SFC,
flow charting and more (6 languages supported)
 High Level C programming
ETHERNET PORT
 10/100BaseTx (auto-detecting)
 RJ45 connection (auto-crossover)
 Protocols TCP/IP, ARP, UDP, ICNP, DHCP, Modbus/TCP,
Sixnet, optionally PPP, DNP3 and more
SERIAL PORT
 Up to 115,200 baud
 RS485 Port A screws (485+, 485-, GND) (2-wire half-duplex)
 RS232 Port B RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR, GND)
 RS232 Port C Screws (TD, RD, RTS, GND)
 RS232 Port D (optional) Screws (TD, RD, GND) – In place of
the two analog inputs
 Protocols Master & slave modes; Sixnet & Modbus RTU/
ASCII; Others available as Linux applications
DISCRETE INPUTS
 8 channels sourcing or sinking (jumper/software selectable)
 Guaranteed ON voltage 9 VDC (The threshold is factory
adjustable to turn on at a lower voltage – contact Sixnet)
 Maximum voltage 30 VDC
 Guaranteed OFF voltage 5.0 VDC & 1.5 mA DC
 Input resistance & current 10K Ohms and 3 mA @ 24 VDC
 Filtered ON/OFF delay 25 mS (20 Hz max. counting) for
contact bounce filtering
 Fast ON/OFF delay 4 mS (100 Hz max. counting)
 Count rate (see above) (10 KHz on channel 1 only)
 Counter modes pulse, rate and run time
 Poll time (all channels) 5 mS to 20 mS configuration dependent
DISCRETE OUTPUTS
 4 channels – sourcing 10-30 VDC
 Min. & max. output load 1 mA to 1 Amp sourcing per channel
 Max. OFF state leakage 0.05 mA
 Inrush current 5 Amps (100 mS surge)
 Typical ON characteristics 0.3 Ohms resistance and 0.3 VDC
voltage drop @ 1A
 Poll time (all channels) 5 mS to 20 mS configuration dependent
ANALOG INPUTS
2 channels – current or voltage selectable
Full scale range 4-20 mA or 0-5 VDC (jumper selectable)
A/D and input resolution 16 bits (0.003%); 2 uA (current range)
or 0.5 mV (voltage range)
Full scale accuracy +/-0.1% (@20°C) (factory calibration)
Span & offset temp. coeff. +/-50 ppm per °C
Input impedance 100 Ohm (current range), 80 K Ohm voltage
Current protection Self-resetting fuses (for 4-20 mA range)
DMRR 66 dB at 50/60 Hz (differential mode rejection)
Fastest update time 50 mS (both channels) – configurable for
longer integration times for better noise filtering
ENVIRONMENTAL
 DIN rail or flat panel mount
 Input power 10-30 VDC
 Input current 100 mA @ 24 VDC (typical)
 Temperature -40 to 70°C (-40 to 85°C storage)
 Humidity 5% to 95% RH (non-condensing)
 Flammability UL 94V-0 materials
 Electrical safety UL 508, CSA C22.2/14; EN610101; (IEC1010)
 EMI emissions FCC part 15, ICES-003, Class A; EN55022;
EN61326-1
 EMC immunity EN61326-1 (EN61000-4-2,3,4,6)
 Vibration IEC68-2-6000
 Hazardous locations (Class 1, Div 2, Groups A,B,C,D) UL
1604, CSA C22.2/213, Cenelec EN50021 Zone 2
All specifications are subject to change. Consult factory for latest info.
SOLUTIONS FOR YOUR INDUSTRIAL NETWORKING CHALLENGES
WWW.SIXNET.COM