VT-UIPM-431-H Datasheet, PDF (1/2 Pages) Red Lion Controls. Inc – Industrial RTU | |||
|
MICRO-Versa TRAK µlPmâ¢
Sixnet Automation Devices
PRODUCT DATASHEET
VT-UIPM-
MICRIOnd-VuesrtrsiaTl RTAUK uIPmTM
An Installation-ready Interface for Real-time Plant Floor Data
PRODUCT HIGHLIGHTS
ï® Plant ï¬oor interface for Real-time inventory management,
Remote process monitoring, HVAC & energy management,
environmental monitoring, low cost OEM applications
ï® Ideal for ID tag applications, serial ports link to code readers
ï® Datalogging and timestamping trending, alarm logging, &
transaction recording
ï® Stand alone control of remote sites, IEC 61131 ISaGRAF and
also C++ programming via open source Linux
ï® Limitless multi-user connectivity telephone, Internet, and
wireless telemetry, 10/100 Ethernet plus up to 4 com ports
ï® Embedded Linux open source software, add applications,
I/O drivers & much more
ï® An OEMâs dream platform, pre-certiï¬ed, add your application
PERFORMANCE SPECIFICATIONS
ï® Industrial PowerPC (32 bit data bus)
ï® Operating system embedded open-source Linux
ï® Dynamic memory (RAM) 16 Mbytes for program execution,
dynamic variables, dynamic ï¬le system, etc.
ï® Program memory (Flash) 16 Mbytes for Linux OS, program
storage and ï¬le system
ï® Retained memory (RAM) 512K (battery-backed) for
datalogging and retained variables
ï® Real-time clock battery-backed for time stamping and other
operations
ï® Local I/O (on-board) 12 or 14 (see ordering info.)
ï® I/O Expansion (up to 256) RS485 or Ethernet
ï® Datalogging support
ï® IEC 61131 programming, ISaGRAF for ladder logic, SFC,
ï¬ow charting and more (6 languages supported)
ï® High Level C programming
ETHERNET PORT
ï® 10/100BaseTx (auto-detecting)
ï® RJ45 connection (auto-crossover)
ï® Protocols TCP/IP, ARP, UDP, ICNP, DHCP, Modbus/TCP,
Sixnet, optionally PPP, DNP3 and more
SERIAL PORT
ï® Up to 115,200 baud
ï® RS485 Port A screws (485+, 485-, GND) (2-wire half-duplex)
ï® RS232 Port B RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR, GND)
ï® RS232 Port C Screws (TD, RD, RTS, GND)
ï® RS232 Port D (optional) Screws (TD, RD, GND) â In place of
the two analog inputs
ï® Protocols Master & slave modes; Sixnet & Modbus RTU/
ASCII; Others available as Linux applications
DISCRETE INPUTS
ï® 8 channels sourcing or sinking (jumper/software selectable)
ï® Guaranteed ON voltage 9 VDC (The threshold is factory
adjustable to turn on at a lower voltage â contact Sixnet)
ï® Maximum voltage 30 VDC
ï® Guaranteed OFF voltage 5.0 VDC & 1.5 mA DC
ï® Input resistance & current 10K Ohms and 3 mA @ 24 VDC
ï® Filtered ON/OFF delay 25 mS (20 Hz max. counting) for
contact bounce ï¬ltering
ï® Fast ON/OFF delay 4 mS (100 Hz max. counting)
ï® Count rate (see above) (10 KHz on channel 1 only)
ï® Counter modes pulse, rate and run time
ï® Poll time (all channels) 5 mS to 20 mS conï¬guration dependent
DISCRETE OUTPUTS
ï® 4 channels â sourcing 10-30 VDC
ï® Min. & max. output load 1 mA to 1 Amp sourcing per channel
ï® Max. OFF state leakage 0.05 mA
ï® Inrush current 5 Amps (100 mS surge)
ï® Typical ON characteristics 0.3 Ohms resistance and 0.3 VDC
voltage drop @ 1A
ï® Poll time (all channels) 5 mS to 20 mS conï¬guration dependent
ANALOG INPUTS
ï®ï 2 channels â current or voltage selectable
ï®ï Full scale range 4-20 mA or 0-5 VDC (jumper selectable)
ï®ï A/D and input resolution 16 bits (0.003%); 2 uA (current range)
or 0.5 mV (voltage range)
ï®ï Full scale accuracy +/-0.1% (@20°C) (factory calibration)
ï®ï Span & offset temp. coeff. +/-50 ppm per °C
ï®ï Input impedance 100 Ohm (current range), 80 K Ohm voltage
ï®ï Current protection Self-resetting fuses (for 4-20 mA range)
ï®ï DMRR 66 dB at 50/60 Hz (differential mode rejection)
ï®ï Fastest update time 50 mS (both channels) â conï¬gurable for
longer integration times for better noise ï¬ltering
ENVIRONMENTAL
ï® DIN rail or ï¬at panel mount
ï® Input power 10-30 VDC
ï® Input current 100 mA @ 24 VDC (typical)
ï® Temperature -40 to 70°C (-40 to 85°C storage)
ï® Humidity 5% to 95% RH (non-condensing)
ï® Flammability UL 94V-0 materials
ï® Electrical safety UL 508, CSA C22.2/14; EN610101; (IEC1010)
ï® EMI emissions FCC part 15, ICES-003, Class A; EN55022;
EN61326-1
ï® EMC immunity EN61326-1 (EN61000-4-2,3,4,6)
ï® Vibration IEC68-2-6000
ï® Hazardous locations (Class 1, Div 2, Groups A,B,C,D) UL
1604, CSA C22.2/213, Cenelec EN50021 Zone 2
All speciï¬cations are subject to change. Consult factory for latest info.