3 / //  / 600-VC6DT2
Application data
//  Engine
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Max Power: Prime: bhp (kWm)
Regulation
Frequency
Air Cleaner
//  Liquid Capacity (Lubrication)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
//  Electrical
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
//  Fuel System
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: ft (m)
Recommended Fuel
Total Fuel Flow: gal/hr (lit/hr)
Volvo Penta
TWD1643GE
4-Cycle
6-Inline
984 (16.1)
5.67 (14.4)
6.5 (16.5)
16.5:1
1,800
EMS 2
917 (684)
796 (594)
±.25%
60 Hz
Dry
12.7 (48)
8.7 (33)
25.1 (95)
24
1,155
3/4” NPT
1/2” NPT
3.5 (1)
Diesel #2
55.5 (210)
//  Fuel Consumption
At 100% of Power Rating: gal/hr (lit/hr)
At 75% of Power Rating: gal/hr( lit/hr)
At 50% of Power Rating: gal/hr (lit/hr)
STANDBY
43.1 (163)
31.2 (118)
21.1 (80)
PRIME
37.5 (142)
30.1 (114)
18.5 (70)
//  Cooling - Radiator System
STANDBY
Ambient Capacity of Radiator: °F (°C) 122 (50)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H20 (kPa) 0.8 (0.2)
Water Pump Capacity: gpm (lit/min)
121 (458)
Heat Rejection to Coolant: BTUM (kW) 15,355 (270)
Heat Rejection to After Cooler: BTUM (kW) 7,677 (135)
Heat Radiated to Ambient: BTUM (kW) 4,327 (76)
PRIME
122 (50)
2.4 (0.6)
121 (458)
13,990 (246)
7,109(125)
3,511 (61.7)
//  Air Requirements
Aspirating: *SCFM (m3/min)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m3/min)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m3/min)
STANDBY PRIME
1,937 (54.9) 1,874 (53.1)
23,277 (659) 23,277 (659)
9,759 (278) 7,917 (226)
* Air density = 0.0739 lbm/ft3 (1.184 kg/m3)
//  Exhaust System
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m3/min)
Maximum Allowable
Back Pressure: in. H20 (kPa)
STANDBY
862 (461)
PRIME
792 (422)
4,594 (130.1) 4,202 (119)
40.2 (10) 40.2 (10)