English
Language : 

30-GC6NLT1 Datasheet, PDF (3/4 Pages) MTU Onsite Energy Corporation – GAS Engine-Generator Set
3 / //  / 30-GC6NLT1
Application data
//  Engine
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Speed Regulation
Frequency
Air Cleaner
//  Liquid Capacity (Lubrication)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
//  Electrical
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
//  Fuel Inlet
Fuel Supply Connection Size
Fuel Supply Pressure: in. H20 (mm H20)
GM
3.0L
4-Cycle
4-Inline
181 (3)
4 (10.2)
3.6 (9.1)
9.25:1
1,800
Bosch
51.5 (38.4)
±1%
60 Hz
Dry
//  Fuel Consumption (NG-1000 BTU/ft3 / LP-2500 BTU/ft3)
At 100% of Power Rating: ft3/hr (m3/hr)
At 75% of Power Rating: ft3/hr (m3/hr)
At 50% of Power Rating: ft3/hr (m3/hr)
NG
361 (10.2)
270 (7.7)
189 (5.4)
LPG
159 (4.5)
120 (3.4)
84 (2.4)
//  Cooling - Radiator System
Ambient Capacity of Radiator: °F (°C)
122 (50)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H20 (kPa)
Water Pump Capacity: gpm (lit/min)
0.5 (0.12)
17 (64.4)
Heat Rejection to Coolant: BTUM (kW)
1,436 (25.3)
Heat Radiated to Ambient: BTUM (kW)
886 (15.6)
1.3 (4.9)
1 (3.8)
3.9 (14.8)
12
600
3/4” NPT
7–11 (178–279)
//  Air Requirements
Aspirating: *SCFM (m3/min)
94.3 (2.7)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m3/min)
2,882.39 (81.6)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise *SCFM: (m3/min)
1,998 (56.6)
* Air density = 0.0739 lbm/ft3 (1.184 kg/m3)
//  Exhaust System
Gas Temp. (Stack): °F (°C)
1,300 (704.4)
Gas Volume at Stack
Temp: CFM (m3/min)
304.53 (8.6)
Maximum Allowable
Back Pressure: in. H20 (kPa)
40 (10)