150-JS6DT3 Datasheet, PDF (3/4 Pages) MTU Onsite Energy Corporation – Diesel Engine-Generator Set
3 / //  / 150-JS6DT3
Application data
//  Engine
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Regulation
Frequency
Air Cleaner
//  Liquid Capacity (Lubrication)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
//  Electrical
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
//  Fuel System
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: ft (m)
Recommended Fuel
Total Fuel Flow: gal/hr (lit/hr)
John Deere
6068HF285
4-Cycle
6-Inline
415 (6.8)
4.19 (10.6)
5 (12.7)
19:1
1,800
JDEC
237 (177)
±1%
60 Hz
Dry
5.28 (20)
3.25 (12.3)
6 (22.7)
12
800
3/8” NPT
3/8” NPT
10 (3)
Diesel #2
28.3 (107.2)
//  Fuel Consumption
At 100% of Power Rating: gal/hr (lit/hr)
At 75% of Power Rating: gal/hr( lit/hr)
At 50% of Power Rating: gal/hr (lit/hr)
11.8 (44.7)
9.2 (34.8)
6.7 (25.4)
//  Cooling - Radiator System
Ambient Capacity of Radiator: °F (°C)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H20 (kPa)
Water Pump Capacity: gpm (lit/min)
Heat Rejection to Coolant: BTUM (kW)
Heat Radiated to Air to Air: BTUM (kW)
Heat Radiated to Ambient: BTUM (kW)
122 (50)
0.5 (0.12)
48 (180)
5,324 (93.5)
1,821 (32)
1,461 (26)
//  Air Requirements
Aspirating: *SCFM (m3/min)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m3/min)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m3/min)
* Air density = 0.0739 lbm/ft3 (1.184 kg/m3)
480 (13.6)
17,712 (502)
3,295 (94)
//  Exhaust System
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m3/min)
Maximum Allowable
Back Pressure: in. H20 (kPa)
941 (505)
1,201 (34)
30 (7.5)