QS40.241 Datasheet, PDF (8/28 Pages) PULS GmbH – 24V, 40A, SINGLE PHASE INPUT
Q-Series
QS40.241
24V, 40A, SINGLE PHASE INPUT
7. HOLD-UP TIME
Hold-up Time
typ.
min.
typ.
min.
AC 100V
54ms
45ms
27ms
23ms
AC 120V
54ms
45ms
27ms
23ms
AC 230V
54ms
45ms
27ms
23ms
at 24V, 20A, see Fig. 7-1
at 24V, 20A, see Fig. 7-1
at 24V, 40A, see Fig. 7-1
at 24V, 40A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage
Hold-up Time
60ms
50ms
40ms
24V, 20A, typ.
24V, 20A, min.
30ms
24V, 40A, typ.
20ms
24V, 40A, min.
10ms
0
Input Voltage
90 120 155 190 230Vac
Fig. 7-2 Shut-down behavior, definitions
Input
Voltage
Zero Transition
Output
Voltage
Hold-up Time
- 5%
Oct. 2014 / Rev. 1.2 DS-QS40.241-EN
All parameters are specified at 24V, 40A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/28