English
Language : 

CS10.242 Datasheet, PDF (7/25 Pages) PULS GmbH – SINGLE PHASE INPUT
C-Line
CS10.242
24V, 10A, SINGLE PHASE INPUT
6. OUTPUT
Output voltage
nom. 24V
Adjustment range
min. 24-28V
guaranteed
max. 30V**)
at clockwise end position of potentiometer
Factory settings
typ. 24.1V
±0.2%, at full load, cold unit,
Line regulation
Load regulation
max. 70mV
max. 100mV
90-132 / 180-300Vac
static value, 0A Æ 10A; see Fig. 6-1
Ripple and noise voltage
max. 50mVpp
20Hz to 20MHz, 50Ohm
Output current
nom. 10A
at 24V, ambient temperature <60°C, see Fig. 6-1
nom. 7.5A
at 24V and 70°C ambient temperature
nom. 8.6A
at 28V, ambient temperature <60°C, see Fig. 6-1
nom. 6.5A
at 28V and 70°C ambient temperature
Reduce output current linearly between +60°C and +70°C
Short –term output current
nom. 12A
at 24V, max 1 minute every 10 minutes in average
nom. 10.3A
at 28V, max 1 minute every 10 minutes in average
Output power
nom. 240W
continuously available
Short –term output power
nom. 288W
max 1 minute every 10 minutes in average
Overload behavior
continuous current see Fig. 6-1
Short-circuit current
min. 14A*)
load impedance <100mOhm, see Fig. 6-1
max. 18A*)
load impedance <100mOhm, see Fig. 6-1
Output capacitance
typ. 7 000μF
included inside the power supply
*)
Discharge current of output capacitors is not included.
**) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not a
guaranteed value which can be achieved. The typical value is about 28.5V.
Fig. 6-1 Output voltage vs. output current,
typ.
Output Voltage
28V
Adjustment
Range
24
20
16
12
8
4
0
0
24
+60°C
+25°C
-25°C
Output Current
6 8 10 12 14 16 18 20A
Jul. 2015 / Rev. 2.0 DS-CS10.242-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/25