QS10.241-60 Datasheet, PDF (4/27 Pages) PULS GmbH – 24V, 200W, DC/DC CONVERTER
Q-Series
QS10.241-60
24V, 200W, DC/DC CONVERTER
3. AC-INPUT
Do not operate this DC/DC converter with an AC-input voltage. Use the QS10.241 or QS10.241-C1 unit instead.
4. DC-INPUT
Use a battery or a similar DC source. A supply from the intermediate DC-bus of a frequency converter is not
recommended and can cause a malfunction or damage the unit.
Input voltage
Input voltage range
Input current
Allowed voltage between input
to earth (ground)
Slew rate for voltage between
input to earth (ground)
Allowed input ripple voltage
Turn-on voltage
Shut-down voltage
Start-up delay
Rise time
Turn-on overshoot
External input protection
nom.
typ.
max.
DC 110V
77-154Vdc
66-77Vdc
1.96A
375Vdc
-30%/+40%
short term for 100ms
at 8.3A and 110Vdc input voltage, see Fig. 4-3
continuous, IEC 62103
± 600V
max. 1000V/μs
peak value, allowed for transients
max. 15Vpp
3Vpp
50Hz –10kHz
10kHz – 50kHz
typ. 71Vdc
steady-state value, at ambient temperatures between
-40°C and +70°C, see Fig. 4-1
typ. 61Vdc
steady-state value, see Fig. 4-1
typ. 500ms
see Fig. 4-2
typ. 20ms
at 8.3A constant current load, 0mF load capacitance,
see Fig. 4-2
typ. 45ms
at 8.3A constant current load, 8mF load capacitance,
see Fig. 4-2
max. 200mV
see Fig. 4-2
See recommendations in chapter 23.4.
POUT
Fig. 4-1 Input voltage range
Rated
input range
max.
500ms
Fig. 4-2 Turn-on behavior, definitions
Input
Voltage
VIN
77V
154V
375Vdc
Output
Voltage
- 5%
Start-up Rise
delay Time
Aug. 2016 / Rev. 1.0 DS-QS10.241-60-EN
All parameters are specified at 24V, 8.3A, 110Vdc, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/27