CPS20.121 Datasheet, PDF (4/26 Pages) PULS GmbH – 12V, 30A, SINGLE PHASE INPUT
C-Series
CPS20.121
12V, 30A, SINGLE PHASE INPUT
3. AC-INPUT
AC input
AC input range
Allowed voltage L or N to earth
Input frequency
Turn-on voltage
Shut-down voltage
nom.
min.
min.
max.
nom.
typ.
typ.
typ.
typ.
AC 100-240V
85-264Vac
264-300Vac
300Vac
50–60Hz
84Vac
33Vac
45Vac
62Vac
suitable for TN-, TT- and IT mains networks
continuous operation, no damage between 0 and 85Vac
< 500ms
continuous, IEC 62103
±6%
steady-state value, see Fig. 3-1
steady-state value at 7.5A load, see Fig. 3-1
steady-state value at 15A load, see Fig. 3-1
steady-state value at 30A load, see Fig. 3-1
AC 100V
AC 120V
AC 230V
Input current
typ.
4.0A
3.3A
1.8A
at 12V, 30A, see Fig. 3-3
4.4A
3.7A
2.0A
at 15V, 27A
Power factor*)
typ.
0.99
0.99
0.95
at 12V, 30A, see Fig. 3-4
Crest factor**)
typ.
1.5
1.5
1.65
at 12V, 30A
Start-up delay
typ.
900ms
850ms
700ms see Fig. 3-2
Rise time
typ.
72ms
72ms
72ms
at 12V, 30A const. current
load, 0mF load capacitance,
see Fig. 3-2
typ.
120ms
120ms
120ms
at 12V, 30A const. current
load, 30mF load capacitance,
see Fig. 3-2
Turn-on overshoot
max.
200mV
200mV
200mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
POUT
Fig. 3-1 Input voltage range
Rated
input range
max.
500ms
Fig. 3-2 Turn-on behavior, definitions
Input
Voltage
VIN
85V
264V 300Vac
Output
Voltage
- 5%
Start-up Rise
delay Time
Apr. 2014 / Rev. 1.4 DS-CPS20.121-EN
All parameters are specified at 12V, 30A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.