English
Language : 

YR80.242 Datasheet, PDF (17/17 Pages) PULS GmbH – DUAL REDUNDANCY MODULE
Y-Series
YR80.242
12-28V, 80A, DUAL REDUNDANCY MODULE
17.6. MOUNTING ORIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1
Curve A2
Recommended output current.
Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 17-3
Mounting
Orientation A
(Standard
orientation)
OUTPUT
YR80.242
Redundancy
Module
INPUTS
Output Current
80A
A1
60
40
20
0
10
Ambient Temperature
20 30 40 50
60°C
Fig. 17-4
Mounting
Orientation B
(Upside down)
Output Current
80A
A1
60
40
20
0
10
Ambient Temperature
20 30 40 50
60°C
Fig. 17-5
Mounting
Orientation C
(Table-top
mounting)
Output Current
80A
60
40
20
0
10
Ambient Temperature
20 30 40 50
A2
A1
60°C
Fig. 17-6
Mounting
Orientation D
(Horizontal cw)
Output Current
80A
A2
60
40
20
0
10
Ambient Temperature
20 30 40 50
A1
60°C
Fig. 17-7
Mounting
Orientation E
(Horizontal ccw)
Output Current
80A
A2
60
40
20
0
10
Ambient Temperature
20 30 40 50
A1
60°C
Apr. 2014 / Rev. 1.1 DS-YR80.242-EN
All parameters are specified at 24V, 80A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
17/17