QT20.241 Datasheet, PDF (14/27 Pages) PULS GmbH – THREE PHASE INPUT
Q-Series
QT20.241, QT20.241-C1
24V, 20A, THREE PHASE INPUT
Switching Frequencies
Switching frequency 1
Switching frequency 2
Switching frequency 3
The power supply has three converters with three different switching frequencies
included. One is nearly constant. The others are input voltage and load dependent.
100kHz
Resonant converter, nearly constant
30kHz to 90kHz
Boost converter, load dependent
40kHz to 220kHz PFC converter, input voltage and load dependent
15. ENVIRONMENT
Operational temperature*) -25°C to +70°C (-13°F to 158°F)
Reduce output power according Fig. 15-1
Storage temperature
-40 to +85°C (-40°F to 185°F)
For storage and transportation
Output de-rating
12W/°C
60-70°C (140°F to 158°F)
Humidity**)
5 to 95% r.H.
IEC 60068-2-30
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Vibration random
0.5m²(s³)
2 hours / axis
IEC 60068-2-64
Shock
30g 6ms, 20g 11ms
IEC 60068-2-27
3 bumps / direction, 18 bumps in total
Altitude
0 to 2000m (0 to 6 560ft)
Without any restrictions
2000 to 6000m (6 560 to 20 000ft)
Reduce output power or ambient
temperature, see Fig. 15-2
IEC 62103, EN 50178, overvoltage category II
Altitude de-rating
30W/1000m or 5°C/1000m
> 2000m (6500ft), see Fig. 15-2
Over-voltage category
III
IEC 62103, EN 62477-1, altitudes up to 2000m
II
For altitudes from 2000m to 6000m
Degree of pollution
2
IEC 62103, EN 62477-1, not conductive
LABS compatibility
The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the
unit. Curves and figures for operation on only 2 legs of a 3-phase system can be found in chapter 22.4.
**) Do not energize while condensation is present.
Fig. 15-1 Output current vs. ambient temp.
Allowed Output
Current at 24V
30A
25
for typ. 4s
20
continuous
15
10
5
0
-25
Ambient Temperature
0
20 40 60 70°C
Fig. 15-2 Output current vs. altitude
Allowed Output
Current at 24V
30A
for typ. 4s
25
20
continuous
15
C
B
A
10
5
0
0
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
2000
4000
Altitude
6000m
Oct. 2016 / Rev. 2.0 DS-QT20.241-EN
All parameters are specified at 24V, 20A, 3x 400Vac, 50Hz, symmetrical mains voltages, 25°C ambient and after a 5 minutes run-in
time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany