English
Language : 

CD5.121 Datasheet, PDF (14/22 Pages) PULS GmbH – DC/DC Converter 12V, 8A
CD-Series
CD5.121
DC/DC Converter 12V, 8A
16. DIELECTRIC STRENGTH
The output voltage is floating and has no ohmic connection to the ground.
Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all phase-
terminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings
to the value in the table below.
Fig. 16-1 Dielectric strength
Type test
A
60s
1500Vac
B
1500Vac
C
500Vac
Input
+
-
B
Output
Factory test
5s
Field test
5s
Cut-off current setting
1500Vac
1000Vac
> 30mA
1500Vac
1000Vac
> 30mA
500Vac
500Vac
> 12mA
A
+
Chassis
C
-
ground
To fulfill the PELV requirements according to EN60204-1 § 6.4.1, we
recommend that either the + pole, the – pole or any other part of
the output circuit shall be connected to the protective earth
system. This helps to avoid situations in which a load starts
unexpectedly or can not be switched off when unnoticed earth
faults occur.
Mar. 2016 / Rev. 1.5 DS-CD5.121-EN
All parameters are specified at 12V, 8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
14/22