English
Language : 

SLR5.100 Datasheet, PDF (1/2 Pages) PULS GmbH – Redundancy
Redundancy with boost
SLR5.100
• Input: AC 230V/115V, DC 210-375V
• Output: 24V/5A
• High overload current, no switch-off
• Quasi-Wide-Range Input
• N+1 redundancy, RDY relay contact
CschBeme
IEC60950
The
Redundant
Variant
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
UL60950 E137006
CUL/CSA-C22.2
No 950-M90
EMC and
Low Volt.
Directive
Input
Output
Input voltage
AC100-120/220-240 V (switchable), 47-63 Hz
(85-132 VAC / 176-264 VAC, 210-375 VDC,
see also „Output: Continuous Loading“)
Quasi-Wide-Range Input: With the switch in the 230V position the pow-
er supply unit operates at low and moderate loads (until 3 A) at any in-
put voltage between 95 and 264 V AC.
Note: At DC input, always leave the switch in the 230V position.
Input current
< 2.6 A (switch in 115V position)
< 1.4 A (switch in 230V position)
• DCin at open output typ. 5 mA (preserves battery sources)
Inrush current
typ. < 15 A at 264 V AC and cold start
To be fused with a 10A, B-type 'circuit-breaker' switch based on the usu-
al thermomagn. overload sensing principle (used anyway to fuse the in-
put lines). In addition, the unit contains an internal fuse (not accessible).
Harmonic current
emissions
acc. to EN 61000-3-2
Rated output voltage 24 V DC
For balanced current sharing during parallel operation:
Soft characteristic (25.2 V DC ±2% at no-load, 24 V DC ±0.5% at nominal
load, almost linear characteristic curve)
Output noise
suppression
Radiated EMI values below EN50081-1, even
when using long, unscreened output cables.
Ambient temperature Operation: -10°C...+70°C (>60°C: Derating)
range Tamb
Storage: -25°C...+85°C
Continuous loading Switch AC/DCin
Iout
(at Tamb= -10°C...+60°C, 230V
convection cooling), see
also diagram overleaf.
For start at Tamb< 0°C and
low input voltage, please
176-264 V
95-176 V
210-375 V
150-210 V
ACin
ACin
DCin
DCin
5A/6A*
3A
5A/6A*
3A
contact PULS.
100-150 V DCin 2 A
Output is protected
115V 85-132 V ACin 5 A / 6 A *
against short circuit,
open circuit and overload
*
short-term 6 A (< 1 min), at 45°C or forced cooling
even continuous
Transient
handling
Hold-up time
Transient resistance acc. to VDE 0160 / W2
(750 V / 1.3 ms), for all load conditions.
> 37 ms at 196 VAC, 24 V / 5 A
(see diagram overleaf)
Efficiency, Reliability etc.*
Efficiency
typ. 89 % (230 VAC, 24 V / 5 A)
Losses
typ. 14.8 W (230 VAC, 24 V / 5 A)
MTBF
480.000 h acc. to Siemensnorm SN 29500
(24 V/5 A, 230 VAC, Tamb = +40 °C)
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
Derating
Voltage regulation
Ripple / Noise
Overvolt. protection
Parallel operation
Front panel indicator
RDY relay contact
• Type
• closes
• opens
• Electrical isolation
• Contact rating
typ. 3 W/K (at Tamb=+60°C...+70°C)
better than 2% Vout overall
< 30 mVPP, (20 MHz bandw., 50 Ω measurem.)
typ. 29 V
yes, current sharing via soft characteristic
(see diagram)
Green LED
normally open contact
when output voltage > 22.1V ±4%
when output voltage < 19.8V ±4%
500V DC to output voltage
1A at 28V DC
Construction / Mechanics*
Housing dimensions and Weight
• WxHxD
64 mm x 124 mm x 102 mm (+ DIN rail)
• Free space for
above/below 25 mm recommended
ventilation
left/right 15 mm recommended
• Weight
620 g
Design advantages:
• Input and output pluggable by means of Combicon® plug connector.
• Ensure strain relief of the plug connectors
when installing the unit.
• Input and output are strictly apart from each other and so cannot be
mixed up (input below, output above).
* For further information see data sheets „The SilverLine“, „SilverLine Family
Branches“ and mechanics data sheet
Order information
Order number
SLR5.100
SL5.100
SLS5.100
SLZ01
Description
N+1 redundancy*
Basic version without redundancy*
Safety Cover*
Screw mounting set, two needed per unit
slr5e100 / 040107
1/2