English
Language : 

SLR10.100 Datasheet, PDF (1/2 Pages) PULS GmbH – Redundancy in square
Redundancy in square
SLR10.100
• Input: AC 230V/115V, DC 240-375 V
• Output: 24 V/10 A
• High overload current, no switch-off
• N+1 redundancy, RDY relay contact
• Robust mechanics and EMC
CschBeme
IEC60950
UL508 LISTED
IND. CONT. EQ.
18 WM, 60°C
UL60950 E137006
CUL/CSA-C22.2
No 950-M90
The
Redundant
Variant
EMC and
Low Volt.
Directive
Input
Output
Input voltage
AC100-120/220-240 V (switchable), 47-63 Hz
(85-132 VAC / 176-264 VAC, 240-375 VDC)
Note: At DC input, always leave the switch in the 230V position.
Input current
< 6 A (switch in 115V position)
< 2.8 A (switch in 230V position)
DCin at open output 8 mA (preserves battery sources)
Rated output voltage 24 V DC
For balanced current sharing during parallel operation:
Soft characteristic (25.2 V DC ±2% at no-load, 24 V DC ±0.5% at nominal
load, almost linear characteristic curve)
Output noise
suppression
Radiated EMI values below EN50081-1, even
when using long, unscreened output cables.
Inrush current
typ. < 30 A at 264 V AC and cold start
Unit is internally fused (fuse not accessible). External fuse not necessary,
but recommended (common 10A, B-type 'circuit-breaker' switch used
anyway to fuse the input lines).
Transient
handling
Transient resistance acc. to VDE 0160 / W2
(750 V / 1.3 ms), for all load conditions.
Hold-up time
> 25 ms at 196 VAC, 24 V / 10 A
(see diagram overleaf)
Ambient temperature Operation: 0°C...+70°C (>60°C: Derating)
range Tamb
Storage: -25°C...+85°C
Rated continuous loading with convection cooling
• Tamb=0°C - 60°C
• Tamb=0°C - 45°C
24 V / 10 A
12 A
short-term also at 60 °C
Output is protected against short circuit, open circuit and overload
Derating
typ. 12 W/K (at Tamb=+60°C...+70°C)
Efficiency, Reliability etc.*
Efficiency
typ. 89 % (230 VAC, 24 V / 10 A)
Voltage regulation
Ripple / Noise
Overvolt. protection
better than 2% Vout overall
< 30 mVPP, (20 MHz bandw., 50 Ω measurem.)
typ. 35 V
Losses
typ. 26.7 W (230 VAC, 24 V / 10 A)
MTBF
390.000 h acc. to Siemensnorm SN 29500
(24 V/10 A, 230 VAC, Tamb = +40 °C)
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics
specified for +105°C (cf. ’The SilverLine’, p.2).
Start / Overload Behaviour
Start-up delay
typ. 0.1 s
Parallel operation
Front panel indicator
RDY relay contact
• Type
• closes
• opens
• Electrical isolation
• Contact rating
yes, current sharing via soft characteristic
(see diagram)
Green LED
normally open contact
when output voltage > 22.1V ±4%
when output voltage < 19.8V ±4%
500V DC to output voltage
1A at 28V DC
Rise time
Overload Behaviour
• Special PULS Over-
load Design (see
diagram overleaf)
• 20% power boost
ca. 5-20 ms, depending on load
* For further information see data sheets „The SilverLine“, „SilverLine Family
– no disconnection, no hiccup if overloaded
Branches“ and mechanics data sheet
– high overload current (up to 1.6 INom), Vout
is gradually reduced with increasing current.
– 12A short-term, at 45°C or forced cooling
even continuous
Advantages:
• High short-circuit current, giving large ’start-up window’: unit starts
reliably even with awkward loads (DC-DC converters, motors).
• No ’sticking’ such as can occur with fold-back characteristics
• Secondary fuses operate reliably
Order information
Order number
SLR10.100
SL10.100
SLS10.100
SLZ01
Description
N+1 redundancy*
Basic version without redundancy*
Safety Cover*
Screw mounting set, two needed per unit
slr10e100 / 031217
1/2