English
Language : 

QT40.241 Datasheet, PDF (1/29 Pages) PULS GmbH – THREE PHASE INPUT
Q-Series
QT40.241, QT40.242
24V, 40A, THREE PHASE INPUT
POWER SUPPLY
ƒ 3AC 380-480V Wide-range Input
ƒ Three Input Fuses Included
ƒ Version with Extra Long Lifetime Available (QT40.242)
ƒ Width only 110mm, Weight only 1.5kg
ƒ 95.3% Full Load and Excellent Partial Load Efficiencies
ƒ 50% BonusPower®, 1440W for up to 4s
ƒ 110A Peak Current for 25ms for Easy Fuse Tripping
ƒ Active PFC (Power Factor Correction)
ƒ Active Filtering of Input Transients
ƒ Negligible Low Input Inrush Current Surge
ƒ Full Power Between -25°C and +60°C
ƒ Current Sharing Feature for Parallel Use
ƒ Remote Control of Output Voltage
ƒ DC-OK Relay Contact
ƒ Shut-down Input
ƒ 3 Year Warranty
GENERAL DESCRIPTION
The most outstanding features of the DIMENSION Q-
Series DIN-rail power supplies are the extremely high
efficiencies and the small sizes, which are achieved by a
synchronous rectification and other technological
designs.
Large power reserves of 150% support the starting of
heavy loads such as DC-motors or capacitive loads. In
many cases this allows the use of a unit from a lower
wattage class which saves space and money.
High immunity to transients and power surges as well as
low electromagnetic emission makes usage in nearly
every environment possible.
The integrated output power manager, the three input
fuses and near zero input inrush current make
installation and usage simple. Diagnostics are easy due
to the DC-ok relay, a green DC-OK LED and the red
overload LED.
A large international approval package for a variety of
applications makes this unit suitable for nearly every
application.
SHORT-FORM DATA
Output voltage
DC 24V
nominal
Adjustment range 24 - 28V
Output current
40 – 34.3A
continuous
60 – 51.5A
short term (4s)
Output power
960W
continuous
1440W
short term (4s)
Output ripple
< 100mVpp
20Hz to 20MHz
Input voltage
3AC 380-480V -15%/+20%
Mains frequency 50-60Hz
±6%
AC Input current 1.65 / 1.35A
at 3x400 / 480Vac
Power factor
0.88 / 0.90
at 3x400 / 480Vac
AC Inrush current typ. 4.5A peak
Efficiency
95.3 / 95.2%
at 3x400 / 480Vac
Losses
47.3 / 48.4W
at 3x400 / 480Vac
Temperature range -25°C to +70°C operational
Derating
24W/°C
+60 to +70°C
Hold-up time
typ. 25 / 25ms at 3x400 / 480Vac
Dimensions
110x124x127mm WxHxD
Weight
1500g / 3.3lb
ORDER NUMBERS
Power Supply QT40.241
QT40.242
Accessory
ZM2.WALL
UF20.241
YR80.241
24-28V Standard unit
24-28V Standard unit
Extra long lifetime
Wall mount bracket
Buffer unit
Redundancy module
MARKINGS
IND. CONT. EQ.
UL 508
UL 60950-1
Class I Div 2
Marine
EMC, LVD, RoHS
Dec. 2016 / Rev. 2.4 DS-QT40.241-EN
All parameters are specified at 24V, 40A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/29