English
Language : 

PIC120.241D Datasheet, PDF (1/22 Pages) PULS GmbH – 24V, 5A, SINGLE PHASE INPUT
PIANO-Series
PIC120.241D
24V, 5A, SINGLE PHASE INPUT
POWER SUPPLY
ƒ AC 100-120V / 200-240V Auto-Select Input
ƒ Cost Optimized without Compromising Quality or
Reliability.
ƒ Width only 39mm
ƒ Efficiency up to 92.3%
ƒ Full Power Between -10°C and +55°C
ƒ DC-OK Relay Contact Included
ƒ 3 Year Warranty
GENERAL DESCRIPTION
These PIANO series units are extraordinarily compact,
industrial grade power supplies that focus on the
essential features needed in today’s industrial
applications. The excellent cost/performance ratio
presents many new and exciting opportunities without
compromising quality or reliability.
The mechanically robust housing is made of a high-
grade, reinforced molded material, which permits the
units to be used in surrounding temperatures up to
70°C.
The unit is equipped with a auto-select input voltage
stage, which makes the unit suitable for global use.
The addition of a DC-OK signal makes the unit suitable
for many industry applications such as: process,
automation and many other critical applications where
preventive function monitoring can help to avoid long
downtimes.
SHORT-FORM DATA
Output voltage
Output
Output ripple
AC Input voltage
DC 24V
24 - 28Vdc
Adjustment range
for AC 110-120 / 220-240V mains:
5.0 - 4.3A
at 24-28V, <55°C
3.1 - 2.7A
at 24-28V, <70°C
for AC 100 / 200V mains:
5.0 - 4.3A
at 24-28V, <50°C
2.5 - 2.1A
at 24-28V, <70°C
< 100mVpp 20Hz to 20MHz
AC 100-120V / ±10%
200-240V
Auto-Select
Mains frequency 50-60Hz
±6%
AC Input current 1.72A / 1.05A at 120/ 230Vac
Power factor
0.64 / 0.54
at 120/ 230Vac
AC Inrush current 22A / 33A peak at 120/ 230Vac, 40°C
Efficiency
91.2% / 92.3% at 120/ 230Vac
Losses
11.6W / 10.0W at 120/ 230Vac
Temp. range
-10°C to +70°C operational
Derating
3W/°C
+55 to +70°C *)
Hold-up time
51ms / 50ms at 120/ 230Vac
Dimensions
39x124x124mm WxHxD
Weight
370g / 0.81lb
*) +50 to +70°C for AC 100V / 200V mains
ORDER NUMBERS
Power Supply PIC120.241D 24-28V Unit
Accessory
YR2.DIODE
UF20.241
Redundancy module
Buffer Module
MARKINGS
IND. CONT. EQ.
UL 508
UL 60950-1
EMC, LVD
Jun. 2016 / Rev. 1.2 DS-PIC120.241D-EN
All parameters are specified at 24V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/22