24V, 5A, SINGLE PHASE INPUT
POWER SUPPLY
ƒ AC 200-240V Regional Input
ƒ Cost Optimized without Compromising Quality or
Reliability.
ƒ Width only 39mm
ƒ Efficiency up to 90.5%
ƒ Low No-load Power Losses
ƒ Full Power Between -10°C and +55°C
ƒ DC-OK Relay Contact Included
ƒ 3 Year Warranty
GENERAL DESCRIPTION
These PIANO series units are extraordinarily compact,
industrial grade power supplies that focus on the
essential features needed in today’s industrial
applications. The excellent cost/performance ratio
presents many new and exciting opportunities without
compromising quality or reliability.
The mechanically robust housing is made of a high-
grade, reinforced molded material, which permits the
units to be used in surrounding temperatures up to
70°C.
Since typical industrial applications do not require
multiple mains inputs, the reduction to a regional input
voltage range (AC 200-240V) simplifies the circuitry and
has significant advantages for reliability, efficiency and
cost.
The addition of a DC-OK signal makes the unit suitable
for many industry applications such as: process,
automation and many other critical applications where
preventive function monitoring can help to avoid long
downtimes.
ORDER NUMBERS
Power Supply
PIC120.241C
PIC120.242C
24-28V Standard unit
with DC-OK contact
24-28V Standard unit
without DC-OK contact
Accessory
YR2.DIODE
UF20.241
Redundancy module
Buffer Module
SHORT-FORM DATA
Output voltage
DC 24V
Adjustment range 24 - 28V
Output current
5A
at 24V, amb <55°C
3.1A
at 24V, amb <70°C
4.3A
at 28V, amb <55°C
2.7A
at 28V, amb <70°C
Output power
120W
ambient <55°C
75W
ambient <70°C
Output ripple
< 100mVpp
20Hz to 20MHz
AC Input voltage AC 200-240V ±10%
Mains frequency 50-60Hz
±6%
AC Input current 1.06A
at 230Vac
Power factor
0.54
at 230Vac
AC Inrush current 28A peak
at 230Vac
Efficiency
90.5%
at 230Vac
Losses
12.6W
at 230Vac
Temperature range -10°C to +70°C operational
Derating
3W/°C
+55 to +70°C
Hold-up time
33ms
at 230Vac
Dimensions
39x124x124mm WxHxD
Weight
350g / 0.77lb
MARKINGS
IND. CONT. EQ.
UL 508
UL 60950-1
EMC, LVD
Marine
Jan. 2016 / Rev. 1.4 DS-PIC120.241C-EN
All parameters are specified at 24V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany