English
Language : 

ML60.241 Datasheet, PDF (1/23 Pages) PULS GmbH – 24V, 2.5A, SINGLE PHASE INPUT
MiniLine-2
ML60.241
24V, 2.5A, SINGLE PHASE INPUT
POWER SUPPLY
ƒ 100-240V Wide Range Input
ƒ NEC Class 2 Compliant
ƒ Adjustable Output Voltage
ƒ Efficiency up to 89.7%
ƒ Low No-load Losses and Excellent Partial-load Efficiency
ƒ Compact Design, Width only 45mm
ƒ Full Power between -10°C and +60°C
ƒ Large International Approval Package
ƒ 3 Year Warranty
GENERAL DESCRIPTION
A compact size, light weight, simple mounting onto the
DIN-rail and the utilization of only quality components
are what makes the MiniLine power supplies so easy to
use and install within seconds.
A rugged electrical and mechanical design as well as a
high immunity against electrical disturbances on the
mains provides reliable output power. This offers
superior protection for equipment which is connected
to the public mains network or is exposed to a critical
industrial environment.
The MiniLine series offers output voltages from 5 to
56Vdc and a power rating from 15W to 120W.
The supplementary MiniLine decoupling diode module
MLY10.241 allows building of redundant systems or to
protect against back-feeding voltages.
ORDER NUMBERS
Power Supply ML60.241
Accessory
MLY10.241
UF20.241
ZM3.WALL
24-28V Standard unit
Redundancy Module
Buffer Module
Wall mount bracket
SHORT-FORM DATA
Output voltage
Adjustment range
Output current
Output power
Output ripple
Input voltage
Mains frequency
AC Input current
Power factor
AC Inrush current
DC 24V
24 - 28V
2.5A at 24V
2.1A at 28V
60W
< 50mVpp
AC 100-240V
50-60Hz
0.98 / 0.58A
0.58 / 0.5
typ. 16 / 32A
DC Input
88-375Vdc
Efficiency
87.8 / 89.7%
Losses
8.3 / 6.7W
Temperature range -10°C to +70°C
Derating
1.5W/°C
Hold-up time
typ. 24 / 107ms
Dimensions
45x75x91mm
Weight
250g / 0.55lb
20Hz to 20MHz
-15% / +10%
±6%
at 120 / 230Vac
at 120 / 230Vac
peak value at 120
/ 230Vac 40°C
and cold start
below 110Vdc
derating required
at 120 / 230Vac
at 120 / 230Vac
operational
+60 to +70°C
at 120 / 230Vac
WxHxD
MARKINGS
Ind. Cont. Eq. UL 508
Class I Div 2
UL 60950-1
NEC
Class 2
Marine
EMC, LVD
Nov. 2015 / Rev. 1.4 DS-ML60.241-EN
All parameters are specified at 24V, 2.5A, 230Vac 50Hz input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/23