English
Language : 

ML100.200 Datasheet, PDF (1/2 Pages) PULS GmbH – 24V 4.2A, TWO-PHASE INPUT
MiniLine
ML100.200
24V 4.2A, TWO-PHASE INPUT
POWER SUPPLY
■ 2AC 380-480V
■ 2 Phase Input
■ No Neutral Wire Required
■ Input Fuse Included
■ Efficiency up to 90.0%
■ Full Output Power Between -10°C and +60°C
■ Quick-connect Spring-clamp Terminals
■ 3 Year Warranty
GENERAL DESCRIPTION
The ML100.200 is a simple and cost effective
approach to convert the AC voltage of a typical
three phase system into a regulated DC voltage. It
only requires two phases and thereby saves terminal
space, terminal cost, wires, fuses and installation
time.
The ML100.200 is very compact, high efficient and
easy to use. The input is internally protected, which
makes external fuses unnecessary in many cases.
Weighing only 360g, it is a lightweight compared to
the 50/60Hz control transformers, which are
commonly used for low-power control voltages
where a neutral wire is not available.
High immunity to transients and power surges as
well as low electromagnetic emission makes usage in
nearly every environment possible.
L1
++
--
DC
ok
L2
24-
28V
L3
ML100.200
PE
L2 L1
SHORT-FORM DATA
Output voltage
Adjustment range
Output current
Output power
Output ripple
DC 24V
24-28V
4.2-3.6A
100W
< 50mVpp
guaranteed
20Hz to 20MHz
Input voltage
2AC 380-480V ±15%
Mains frequency 50-60Hz
±6%
AC Input current typ. 0.46 / 0.4A at 400 / 480Vac
Power factor
typ. 0.6 / 0.55
at 400 / 480Vac
AC Inrush current typ. 36 / 45A
at 400 / 480Vac
Hold-up time
typ. 48 / 85ms
at 400 / 480Vac
DC Input
consult PULS
Efficiency
89.5 / 89.0%
at 400 / 480Vac
Losses
11.7 / 12.3W
at 400 / 480Vac
Temperature range -10°C to +70°C operational
-40°C to +85°C storage, transport
Derating
2.5 W/°C
+60 to +70°C
Humidity
< 95% r.H.
IEC 60068-2-30
Do not energize while condensation is present
Vibration
2g (2 hours/axis) IEC 60068-2-6
Shock
30g 6ms,
20g 11ms
IEC 60068-2-27
Dimensions
72.5x75x103mm WxHxD
ORDER NUMBERS
Power Supply ML100.200 24-28V Power Supply
Accessory
MLY02.100 Decoupling Module
MARKINGS
18WM
LISTED
IND. CONT. EQ.
UL 508
UL 60950-1,
EMC, LVD
ML100.200 Rev 1.0-EN / All parameters are specified at 24V, 4.2A, 400Vac and 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/2