English
Language : 

CS5.241 Datasheet, PDF (1/25 Pages) PULS GmbH – SINGLE PHASE INPUT
C-Line
CS5.241, CS5.241-C1, CS5.241-S1
24V, 5A, SINGLE PHASE INPUT
POWER SUPPLY
ƒ AC 100-120 / 200-240V Auto-select Input
ƒ Width only 32mm
ƒ Optional with Conformal Coated PC-boards (CS5.241-C1)
ƒ Optional with Spring-clamp Terminals (CS5.241-S1)
ƒ Efficiency up to 90.2%
ƒ Easy Fuse Breaking due to High Overload Peak Current
ƒ 20% Output Power Reserves
ƒ Full Power Between -25°C and +60°C
ƒ Minimal Inrush Current Surge
ƒ 3 Year Warranty
GENERAL DESCRIPTION
The DIMENSION C-Line units are cost optimized power
supplies without compromising quality, reliability and
performance. The C-Line is part of the DIMENSION
power supply family, existing alongside the high
featured Q-Line.
The CS5.241 includes all the essential basic functions and
the devices have a power reserve of 20%. This extra
current may even be used continuously at temperatures
up to +45°C.
The most important features are the small size, high
efficiency and the wide temperature range.
The Auto-select input makes worldwide installation and
usage very simple. Defects or system failures caused by
wrongly set switches cannot occur.
High immunity to transients and power surges as well as
low electromagnetic emission and a large international
approval package for a variety of applications makes
this unit suitable for nearly every situation.
SHORT-FORM DATA
Output voltage
DC 24V
Adjustment range 24 - 28V
Output current
5A
at 24V, amb <60°C
6A
at 24V, amb <45°C
4.3A
at 28V, amb <60°C
5.1A
at 28V, amb <45°C
Output power
120W
ambient <60°C
144W
ambient <45°C
Output ripple
< 50mVpp
20Hz to 20MHz
AC Input voltage AC 100-120V / ±10%
200-240V
Auto-select input
Mains frequency 50-60Hz
±6%
AC Input current 2.0 / 1.23A
at 120 / 230Vac
DC Input voltage -
not allowed
Power factor
0.56 / 0.47
at 120 / 230Vac
AC Inrush current 3 / 3A peak
at 120 / 230Vac
Efficiency
89.4 / 90.2% at 120 / 230Vac
Losses
14.5 / 13.2W at 120 / 230Vac
Temperature range -25°C to +70°C operational
Derating *)
3W/°C
+60 to +70°C
Hold-up time
80 / 78ms
at 120 / 230Vac
Dimensions
32x124x117mm WxHxD
Weight
500g / 1.1lb
ORDER NUMBERS
Power Supply CS5.241
CS5.241-C1
CS5.241-S1
Accessory
ZM1.WALL
ZM13.SIDE
YRM2.DIODE
24-28V Standard unit
With conformal coated
pc-boards
with quick-connect
spring-clamp terminals
Wall mount bracket
Side mount bracket
Redundancy module
MARKINGS
IND. CONT. EQ.
UL 508
UL 60950-1
Marine
Class I Div 2
EMC, LVD
Jul. 2015 / Rev. 2.0 DS-CS5.241-EN
All parameters are specified at 24V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/25