English
Language : 

CP20.241 Datasheet, PDF (1/27 Pages) PULS GmbH – 24V, 20A, SINGLE PHASE INPUT
PRELIMINARY
CP-Series
CP20.241, CP20.241-C1,
CP20.241-S1, CP20.241-S2
24V, 20A, SINGLE PHASE INPUT
POWER SUPPLY
ƒ AC 100-240V Wide-range Input
ƒ Width only 48mm
ƒ Efficiency up to 95.6%
ƒ Excellent Partial Load Efficiency
ƒ 20% Output Power Reserves
ƒ Easy Fuse Breaking – 3 times nominal current for 12ms
ƒ Safe HiccupPLUS Overload Mode
ƒ Active Power Factor Correction (PFC)
ƒ Minimal Inrush Current Surge
ƒ Full Power Between -25°C and +60°C
ƒ DC-OK Relay Contact
ƒ Current Sharing Feature for Parallel Use
ƒ 3 Year Warranty
GENERAL DESCRIPTION
The Dimension CP-Series are cost optimized power
supplies without compromising quality, reliability and
performance. The most outstanding features of the
CP20 series are the high efficiency, electronic inrush
current limitation, active PFC, wide operational
temperature range and the extraordinary small size.
The CP20.241-C1 is equipped with conformal coated pc-
boards preferred for applications in harsh areas.
The CP20.241-S1 is equipped with quick-connect spring-
clamp terminals preferred for applications which are
exposed to mechanical vibration.
The CP20.241-S2 is equipped with push-in terminals
optimized for automated cabinet wiring.
The devices have a power reserve of 20% included,
which may even be used continuously at temperatures
up to +45°C.
High immunity to transients and power surges as well as
low electromagnetic emission, a DC-OK relay contact
and a large international approval package for a variety
of applications makes this unit suitable for nearly every
situation.
ORDER NUMBERS
Power Supply
CP20.241
CP20.241-C1 With conformal coated
pc-boards
CP20.241-S1 With quick-connect
spring-clamp terminals
CP20.241-S2 With push-in terminals
Accessory
ZM5.WALL
UF20.241
YR40.242
YR40.245
Wall/Panel mount bracket
Buffer module
Redundancy module
Redundancy module
SHORT-FORM DATA
Output voltage
Adjustment range
Output current
Input voltage AC
Mains frequency
Input current AC
Power factor
Input voltage DC
Input current DC
AC Inrush current
Efficiency
Losses
Hold-up time
Temperature range
Size (WxHxD)
Weight
DC 24V
Nominal
24 - 28V
Factory set 24.1V
24.0 - 20.6A
Below +45°C ambient
20.0 – 17.1A
At +60°C ambient
15.0 – 13.0A
At +70°C ambient
Derate linearely between +45°C and +70°C
AC 100-240V -15%/+10%
50-60Hz
±6%
4.26 / 2.23A
At 120 / 230Vac
0.99 / 0.95
At 120 / 230Vac
DC 110-150V ±20%
4.64A
At 110Vdc
10.0 / 4.5A
At 120 / 230Vac
94.2 / 95.6%
At 120 / 230Vac
29.6 / 22.1W
At 120 / 230Vac
32ms
-25°C to +70°C
48x124x127mm Without DIN-rail
830g / 1.83lb
MARKINGS
IND. CONT. EQ.
UL 508, planned
UL 60950-1, planned
Marine, planned
Class I Div 2, planned
IECEx
ATEX
II 3G Ex ec nC II T3 Gc
planned
EMC, LVD
(ATEX, planned)
May 2017 / Rev. 0.3 DS-CP20.241-EN
All parameters are typical values specified at 24V, 20A output, 230Vac input, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/27