English
Language : 

CP10E242 Datasheet, PDF (1/30 Pages) PULS GmbH – 24V, 10A, 240W, SINGLE PHASE INPUT
CP-Series
CP10.241, CP10.241-C1, CP10.241-S1,
CP10.241-S2, CP10.242
24V, 10A, 240W, SINGLE PHASE INPUT
POWER SUPPLY
ƒ AC 100-240V Wide-range Input
ƒ Width only 39mm
ƒ Efficiency up to 95.2%
ƒ Excellent Partial Load Efficiency
ƒ 20% Output Power Reserves
ƒ Safe HiccupPLUS Overload Mode
ƒ Easy Fuse Breaking due to High Overload Peak Current
ƒ Active Power Factor Correction (PFC)
ƒ Minimal Inrush Current Surge
ƒ Full Power Between -25°C and +60°C
ƒ DC-OK Relay Contact
ƒ 3 Year Warranty
GENERAL DESCRIPTION
The DIMENSION CP-Series units are high-end power
supplies in a medium price range without compromising
quality, reliability and performance. The CP-Series is
part of the DIMENSION power supply family. The most
outstanding features of CP10 series are the high
efficiency, advanced inrush current limitation, active PFC
and the wide operational temperature range.
The CP-Series includes all the essential basic functions.
The devices have a power reserve of 20% included,
which may even be used continuously at temperatures
up to +45°C. Additionally, the CP10 can deliver three
times the nominal output current for at least 12ms
which helps to trip fuses on faulty output branches.
High immunity to transients and power surges as well as
low electromagnetic emission, a DC-OK relay contact
and a large international approval package for a variety
of applications makes this unit suitable for nearly every
situation.
SHORT-FORM DATA
Output voltage
DC 24V
Nominal
Adjustment range 24 – 28V
Factory setting 24.1V
Output current
12.0-10.3A
Below +45°C ambient
10.0-8.6A
At +60°C ambient
7.5-6.5A
At +70°C ambient
Derate linearely between +45°C and +70°C
Input voltage AC AC 100-240V
-15%/ +10%
Mains frequency
50-60Hz
±6%
Input current AC
2.15 / 1.13A
At 120 / 230Vac
Power factor
0.99 / 0.97
At 120 / 230Vac
Input voltage DC
DC 110-150V ±20% For CP10.241 (-xx)
DC 110-300V ±20% CP10.242
Input current DC
2.35A
At 110Vdc
2.35 / 0.84A
At 110 / 300Vdc
Input inrush current 6 / 9A pk
At 40°C 120 / 230Vac
Efficiency
93.6 / 95.2%
At 120 / 230Vac
Losses
16.4 / 12.1W
At 120 / 230Vac
Hold-up time
37 / 37ms
At 120 / 230Vac
Temperature range -25°C to +70°C
Size (w x h x d)
39x124x117mm Without DIN-Rail
Weight
600g / 1.3lb
ORDER NUMBERS
Power Supply CP10.241
CP10.241-C1 Conformal coated pc-boards
CP10.242-S1 Spring-clamp terminals
CP10.241-S2 Push-in terminals
CP10.242 Extended DC-Input range
Mechanical Accessory
ZM4.WALL
ZM12.SIDE
Wall/panel mount bracket
Side mount bracket
MARKINGS
For details and a complete approval list see section 20.
IND. CONT. EQ.
UL 508
UL 60950-1
Class I Div 2
IECEx
ATEX
Marine
Aug. 2017 / Rev. 1.4 DS-CP10.241-EN
All values are typical at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/30