CP10.241-M1 Datasheet, PDF (1/27 Pages) PULS GmbH – 24V, 10A, SINGLE PHASE INPUT | |||
|
CP-Series
CP10.241-M1
24V, 10A, SINGLE PHASE INPUT
POWER SUPPLY
 2MOPP Safety Approved for Medical applications
According to IEC 60601-1, 3rd edition
 EMC Tested for Medical Use According to IEC 60601-1-2,
4th edition
 Quick-connect Spring-clamp Terminals
 AC 100-240V Wide-range Input
 Width only 39mm
 Efficiency up to 95.2%, Excellent Partial Load Efficiency
 20% Output Power Reserves
 Safe HiccupPLUS Overload Mode
 Easy Fuse Breaking due to High Overload Peak Current
 Active Power Factor Correction (PFC)
 Minimal Inrush Current Surge
 Full Power Between -25°C and +60°C
 DC-OK Relay Contact
 3 Years Limited Warranty
GENERAL DESCRIPTION
The CP10.241-M1 is a DIN-rail mountable single-phase-
input power supply for industrial use and for use in
medical equipment. It provides a stabilized and
galvanically separated SELV/PELV output voltage.
The specialty of this power supply is the 2MOPP (two
means of patient protection) safety approval for
medical use and the fulfillment of the required EMC
tests for professional healthcare facility and home
healthcare environments.
The CP-Series is part of the DIMENSION power supply
family. The most outstanding features of CP10.241-M1
are the high efficiency, advanced inrush current
limitation, active PFC and the wide operational
temperature range.
High immunity to transients and power surges as well as
low electromagnetic emission, a DC-OK relay contact
and a large international approval package for a variety
of applications makes this unit suitable for nearly every
situation.
ORDER NUMBERS
Power Supply CP10.241-M1 Medical approved device
Accessory ZM12.SIDE Side mount bracket
SHORT-FORM DATA
Output voltage
DC 24V
Adjustment range 24 â 28V
Factory setting 24.1V
Output current
12 â 10.3A
Below +45°C ambient
10 â 8.6A
At +60°C ambient
7.5 â 6.5A
At +70°C ambient
Derate linearely between +45°C and +70°C
Input voltage AC
AC 100 - 240V -15%/ +10%
Mains frequency
50 - 60Hz
±6%
AC Input current
2.15 / 1.13A
At 120 / 230Vac
Power factor
0.99 / 0.97
At 120 / 230Vac
Input inrush current 6 / 9A pk
At 40°C 120 / 230Vac
Input voltage DC
DC 110-150V
±20%
Input current DC
2.35A
At 110Vdc
Efficiency
93.6 / 95.2%
At 120 / 230Vac
Power losses
16.4 / 12.1W
At 120 / 230Vac
Hold-up time
37ms
Temperature range -25°C to +70°C Continuous
Size (wxhxd)
39x124x117mm Without DIN-rail
Weight
620g / 1.37lb
MARKINGS
IND. CONT. EQ.
UL 508, planned
UL 60950-1,
planned
EMC, LVD
Medical
2MOPP - IEC 60601-1
May 2017 / Rev. 1.2 DS-CP10.241-M1-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/27
|
▷ |