English
Language : 

FAB9810012-16 Datasheet, PDF (2/3 Pages) Power System Technology – Industrial / Medical
FAB9810012-16
OUTPUT
All voltages are adjustable by potentiometer.
FAB9810012 :
FAB9810013 :
FAB9810014 :
FAB9810015 :
FAB9810016 :
+24V / 2A 48W
+15V / 2A 30W
-15V / 2A 30W
-10V / 2A 20W
+ 5V / 2A 15W
Line regulation
Load regulation
Ripple and noise
Current limit
FAB9810012
FAB9810013
Overvoltage FAB9810014
FAB9810015
FAB9810016
OUTPUT
Typ.
0,02 %
Max.
0,2 %
0,02 %
1%
1%
2%
110 to 140 %
of I nominal
27V
18V
- 18V
- 18V
5,8V
Conditions
Low line to high line ; full load
No load to full load
Peak to peak, nom. Input ; full load
SIGNALS
Output OK :
led
ENVIRONMENTAL
Storage temperature :
Operating temperature :
-25°C to +85°C
-10°C to +50°C ambiant, Nominal Power
2/3