English
Language : 

PDF016T Datasheet, PDF (2/2 Pages) PowerDynamics, Inc – 3-PHASE, CHASSIS MOUNT WITH TERMINAL BLOCK EMI/RFI LINE FILTER.
PDF Series Attenuation Table
Non-Medical Applications
Insertion loss in dB (50 Ohm circuit)
PDI
Current
L
P/N Rating (A) (mH x 3)
PDF016T
16
11
PDF032T
32
10
PDF050T
50
4.3
PDF100T
100
4.3
Cx
Cy
(uF x 3) (uF x 4)
2.2
4.4
2.2
4.4
2.2
4.4
2.2
4.4
Cz
(uF x 3)
0.068
0.068
0.068
0.068
R
(Ohms)
100K
100K
100K
100K
Comm. Mode(L-G) MHz
.15 .5 1 5 10 30
85 90 80 73 69 71
84 88 80 62 68 64
80 86 80 70 69 40
75 88 78 64 60 47
Diff. mode(L-L) MHz
.15 .5 1 5 10 30
80 98 79 78 70 57
75 94 78 75 70 57
73 101 90 90 89 61
63 80 74 70 60 40
SCHEMATIC
Cx
Cz
L1
L2
L3
E
Cy R
L1'
L2'
L3'
E'
145 Algonquin Parkway, Whippany, NJ 07981 • 973-560-0019 • FAX: 973-560-0076