English
Language : 

PSE250 Datasheet, PDF (1/2 Pages) Powerbox – 150 - 250 WATTS DC/DC SINGLE OUTPUT
PSE250 Series
150-250 WATTS DC/DC SINGLE OUTPUT
Features
• Under voltage logic alarm.
• Conformally coating, tropic.
• Reverse input voltage protection.
• High efficiency.
• Fully enclosed, meets IP30 standard.
• Convectional cooled.
Specifications
INPUT
Voltage
See table
Reverse voltage protection Yes.
Isolation
Input – Output: 2.5kVac / 4kVdc
Input – Case: 2.5kVac / 4kVdc
Output – Case: 2kVdc
OUTPUT
Voltage
See table.
Current
See table.
Source regulation
0.2%.
Load regulation
0.2% (0-100% load)
Output ripple (100kHz)
10mV p-p (typical)
Voltage adjustment
90% - 110%.
Current limit protection 105%.
Under voltage logic alarm 90% of nominal output.
Soft start
Yes.
Start-up time
1s.
Hold-up time
2-10ms
Efficiency
>88%
ENVIRONMENTAL
Operating temperature
-25°C to +70°C (100% load, O/P > 10V).
-25°C to +55°C (100% load).
Temperature coefficient 0.02% / °C.
Storage temperature
-40°C to 85°C.
Conformal coating
Conformal coated to withstand non-condensing
tropical environment.
MECHANICAL
Mechanical dimensions
PSE150, PSE200 3U x 8TE x 167mm
PSE250 3U x 10TE x 167mm
Weight
0.8.5kg
GENERAL
Cooling
Optional features
STANDARDS
Safety
EMI standards
C-Tick
EMC standards
Convectional cooling.
-Overvoltage protection, option A.The output
voltage is limited to 15% nominal output voltage.
A thyristor short-circuits the output.
-Undervoltage alarm with relay, option B The
logic alarm output is replaced with a relay with
selectable alarm logic NO or NC.
-Built in series diode, option C. A series diode
on the output, when output is connected in
parallel with other power supplies to achieve
redundancy. Output power is derated by 20%.
-Remote sense, option S. The voltage sensing
can be put at the load to compensate for voltage
drop.
-Inrush current limit with NTC, option H Only for
C -input code. Reduce the inrush current during the
start up. The input voltage range will be affected.
- 2.5kVac isolation input/case, option E1. On 24,
36 & 48V inputs The emission level increase to level A.
- 2.5kVac isolation output/case, option E2.
The emission level will increase to level A.
-Train input, option T. Input voltage range
according to train Standard EN50155 and IEC
60751.
- Euro panel, option L 8TE for PSE 150 & PSE
200, 10TE for PSE 250.
- Wall mounting panels, option N. Wall
mounting panel with connector holder The female
connector has to be chosen.
- H15 screw type female, H15-S
- H15 fast-on 6.3mm female, H15-T
- Din rail TS35 clips, option Q.
IEC60950-1: 2001
EN55011/EN55022 class B, IEC/EN61000-6-2,
AS/NZS CISPR11: 2002 Group1 Class A
EN61000-6-2, EN/IEC61000-4-4, EN61000-4-5