English
Language : 

PBMPLS-RM Datasheet, PDF (1/2 Pages) Powerbox – D C / A C S I N EWA V E I N V E R T E R
PBMPLS-RM Series
DC/AC SINEWAVE INVERTER
FEATURES
• 500W - 7000W
• True Sinewave Output
• Massive Overload Capability
• High Efficiency Toroidal TRX
• CCT Breaker/ Batt Isolator Switch
• Rack Mounting
SPECIFICATIONS
INPUT
Input Voltage
12V, 24V, 48V, 96V, 120Vdc (Standard).
36V, 72Vdc, and others (Also available).
Voltage range
-20% to +45% of nominal.
OUTPUT
Output Voltage
Output Frequency
240Vac ±4% (Standard)
> 110Vac ±4% (Option)
50/60Hz ±0.1
Output waveform
True sinewave < 4% THD.
Power factor
All conditions.
Crest factor
>4
Overload Capacity
300% 5 Seconds (all models)
120% 30 minutes (110% 12V models)
Load start sensitivity
0-20W
Efficiency
94% Typical
PROTECTION
AC and DC isolation
3500V, via toroidal transformers
Over-load protection
Yes.
Over-temperature protection
Yes.
Short circuit protection
Yes.
Battery under and over
voltage protection
Battery Isolator
Yes.
The circuit breaker is designed for ease of
operation and safety. If the inverter shuts
down due to Overload, Undervolts or
Overvolts, it can be reset by turning the
Circuit Breaker OFF, waiting 10 seconds (or
until LED goes out), then turning it on again
ENVIRONMENTAL
Temperature range
Cooling
-10°C to 50°C
Derate above 40°C by 10%
Thermostatically controlled 2-speed fan.
STANDARDS & APPROVALS
Safety standards
AS3100, AS3000
C-tick
AS/NZS CISPR14, AS/NZS 1044
EMC standards
EN61000-6-1, EN61000-6-3, AS2279,
AS3000, AS3100 and EN55014
ALARMS & INDICATORS
Inverter Operation
Power Indicator
Undervolts/Overvolts
When inverter is switched on all 3 LEDS light up for
one second for system check procedure
Green LED. Flashes when in standby mode (no load
connected). When load applied LED illuminates
continuously
Red LED. In order to protect the battery the inverter
will shutdown after 5 seconds if the battery voltage
falls below its limit (Undervolts) LED remains
continous or exceeds the maximum (Overvolts) LED
will continue to flash.
Over temperature
Red LED, If the internal temperature exceeds safe
operating limits for more than 5 secnds, the inverter
will shut down in Over temp with this LED on
continuously. Allow 5mins for the inverter to cool
and reset the unit.
Over load
Red LED, if the load demands more current than the
inverter can safely supply for more than 5 seconds,
the inverter will shutdown in Overload and this LED
will flash
OPTIONAL FEATURES
CODE
ADD OPTION TO THE END OF INVERTER PART
NUMBER
D
RCD fitted in place of hardware junction box of AC
output.
G
MIL spec conformal coating applied to final
assembly.
R
Ruggedisation for high vibration environment.
K
Automatic transfer switch 25Amp for 1000W to
1800W.
Automatic transfer switch with ON delay timer and
KX
voltage sensing module. 40Amps for 2000W to
4000W and 65Amp for 5000W to 7000W models.
V
AC output voltage e.g. 100-120Vac.
H
Frequency 60Hz
L
C
DC
MECHANICAL
AC connectors
DC Connectors
Dimensions
Weight
"AC OK" alarm relay contact
Twin switched GPO (available only on 1000W to
5000W models).
Twin switched RCD GPO (available only on 1000W to
5000W models).
Screw terminal junction box.
Heavy duty low loss battery leads.
19", 3RU x 350mm – all models
See Selection Table
www.powerbox.com.au - 1800 251 380
www.powerbox.co.nz - 0800 104 480
Doc. No. PBMPLS-RM Rev.D 20-01-16