English
Language : 

PB314A Datasheet, PDF (1/2 Pages) Powerbox – B AT T E R Y C H A R G E R S Y S T E M
PB314A Series
BATTERY CHARGER SYSTEM
FEATURES
• 636 - 1056W PSU for Battery Backup
• DC UPS Connectable
• Digital Display System
• Rack Mounting
• Constant Float Voltage & Current Limit
• Circuit Breakers & Alarm Relays
• Independent Battery Charging Output
• DC OK & Battery OK Alarms
• Battery connected test
• Optional LVD - Battery Low Volts Disconnect
• Optional Network Connected
• Optional Battery Temperature Probe
• OPERATIONS INSTALLATION HANDBOOK AVAILABLE
SPECIFICATIONS
INPUT
Input Voltage
Frequency:
Input Current:
Inrush current:
Line regulation
OUTPUT
Output Voltage
Output Power
Output Current
Load regulation
Ripple
Noise
Overvoltage shutdown
Output short circuit protection
Battery charger short
circuit protection
Load output protection
Battery output protection
Efficiency
PROTECTION
Overvoltage shutdown
Output short circuit protection
Battery charger short
circuit protection
Load output protection
Battery output protection
Isolation
ENVIRONMENT
Operating temperature
Humidity
Cooling
85-264Vac or 120-360Vdc
47 to 63 Hz
4.1A typical 200Vac
40A typical cold start 200Vac
60mV maximum
13.8Vdc, 27.6Vdc, 55.4Vdc
624W - 1056W
See Selection Table
1% typical
160mVp-p maximum
180mVp-p maximum
16.2 to 19.8V latching
Indefinite (Autoresetting)
Indefinite (Autoresetting)
Thermal - Magnetic Circuit Breaker
Thermal - Magnetic Circuit Breaker.
79% typical
16.2 to 19.8V latching
Indefinite (Autoresetting)
Indefinite (Autoresetting)
Thermal - Magnetic Circuit Breaker
Thermal - Magnetic Circuit Breaker.
Input - Output: 3KVac 1 min
Input - Ground: 2KVac 1 min
Output - Ground: 500Vac 1min
-20°C to +71°C
Derating linearly from 50°C to 71°C to
50% power
20-90% relative humidity
(non condensing)
Forced cooling - internal fan
DISPLAY AND ALARMS
DC OK
AC OK
Charger voltage OK alarm
Battery low voltage alarm
LED Green On = OK, Voltage-free
changeover contact (32V, 1A).
Alarm on failure of AC/DC PSU and tripping
of over temperature limit.
Neon Green On = OK, Voltage-free
changeover contact (32V, 1A). Alarm on
mains fail.
LED Green On = OK, Voltage-free
changeover contact (32V, 1A). Alarm on
battery low voltage or on opening of battery
circuit breaker.
11.0V (12V), 22.0V (24V), 44.0V (48V
OPTIONAL FEATURES
Battery LVD disconnect
Option LVD: For 12V and 24V models, not
available in 48V models.
Network enabled
Option N: Internal network card in
conjunction with PB314A becomes a
network enable device combining the
benefits of SNMP V1, XML and an embedded
webpage.
Temperature compensation
Option T: Temperature probe 2.5M cable
Option T5: Temperature probe 5M cable
Float voltage set to 2.3V per cell at 25°C
with compensation of 3.3mV per cell
Hirose connector
Option H: Circular connector for load and
battery output termination
(Standard model "C" for Cage Clamp
Terminals
STANDARDS & APPROVALS
C-Tick
AS/NZS CISPR11 Group 1 Class A.
Safety
UL 60950 Class 1
EMC
MECHANICAL
Emissions comply with AS/NZ CISPR22
Class-B
AC input socket
IEC320 fused / on off switch
Output termination
Cage clamp terminals (-C version)
Alarm relay contacts
DB25 socket
Load fault current protection 63A circuit breaker
Battery fault current protection 63A circuit breaker
Rack mount size
270 D x 19" W x 2RU H
Weight
5.0 kg
www.powerbox.com.au - 1800 251 380
www.powerbox.co.nz - 0800 104 480
Doc. No. PB314A Rev.K 18-12-15