PB314 Datasheet, PDF (1/3 Pages) Powerbox – 6 3 6 - 7 4 5 WAT T S B AT T E R Y C H A R G E R S Y S T E M
PB314 Series
636-745 WATTS BATTERY CHARGER SYSTEM
FEATURES
• 636 - 745W
• PSU for Battery Backup
• DC UPS Connectable
• Constant Float Voltage & Current Limit
• Circuit Breaker & Alarm Relays
• Optional LVD - Low Volts Battery Disconnect
• OPERATIONS & INSTALLATION HANDBOOK AVAILABLE
SPECIFICATIONS
INPUT
Input Voltage
85-264Vac or 120-360Vdc
Frequency:
47 to 63 Hz
Input Current:
4.1A typical at 200Vac
Inrush current:
40A typical cold start 200Vac
Line regulation
60mV maximum
OUTPUT
Output Voltage
13.8Vdc, 27.6Vdc
Output Power
636W - 745W
Output Current
See Selection Table
Efficiency
79% typical
Load regulation
1% typical
Ripple
160mVp-p max
Noise
180mVp-p max
PROTECTION
Overvoltage shutdown
16.2 to 19.8V latching
Output short circuit
Indefinite protection (Autoresetting)
Battery charger short circuit Indefinite protection (Autoresetting)
Load output protection
Thermal - Magnetic Circuit Breaker
Battery output protection Thermal - Magnetic Circuit Breaker.
Isolation
Input - Output: 3KVac 1 min
Input - Ground: 2KVac 1 min
Output - Ground: 500Vac 1min
ENVIRONMENT
Operating temperature
-20°C to 71°C
Derating from 50°C to 71°C to 50% power
Humidity
Cooling
20-90% relative humidity (non condensing)
Forced cooling - internal fan
DISPLAYS AND ALARMS
DC OK
AC OK
LED Green On = OK, Voltage-free changeover
contact (32V, 1A).Alarm on failure of AC/DC PSU
and tripping of over temperature limit.
LED Green On = OK, Voltage-free changeover
contact (32V, 1A). Alarm on mains fail.
Battery Ok
LED Green On = OK, Voltage-free changeover
contact(32V, 1A). Alarm on battery low voltage or
on opening of battery circuit breaker.
Battery low alarm voltage -11.0Vdc
Battery Low Voltage
Disconnect
Option LVD:
Battery LVD disconnect 10.5V
Battery LVD reconnect 12.0Vdc
Voltage meter
0 to 15Vdc
Load current meter
0 to 100A
Battery current meter -100A to +100A scale.
OPTIONAL FEATURES
Battery Charge Limit
Option BCL: Specify battery charge current based
on battery size.
Battery LVD disconnect
Option LVD: For 12V and 24V models, not
available in 48V models.
STANDARDS & APPROVALS
C-Tick
AS/NZS CISPR11 Group 1 Class A.
Safety
UL 60950 Class 1
EMC
Emissions comply with AS/NZ CISPR22 Class-B
MECHANICAL
AC input socket
IEC320 fused / on off switch
Output termination
Hirose connector (-H version)
Cage clamp terminals (-C version)
Alarm relay contacts
Load fault current
proteciton breaker
Battery fault current
protection breaker
Rack mount size
Weight
DB25 socket
63 A
63 A
264 L x 172 W x 67 H mm
5.0Kg
Doc. No. PB314 Series Rev.J 29-9-15