English
Language : 

GPS-TRIPLE Datasheet, PDF (1/1 Pages) Powerbox – 1 9 5 WAT T L I N E A R
GPS Triple Series
195 WATT LINEAR
FEATURES
• 3 Independent Isolated Output
• Four "3 Digits" LED Display
• 0.01% Load and Line Regulation
• Low Ripple and Noise
• Tracking Operation and Auto Series/Parallel
Operation
• Output ON/OFF Switch
• Output Voltage and Current Setting When Output
Disable
• Fan Speed Control Circuit to Minimize Fan Noise
• Over Load and Reverse Polarity Protection
SPECIFICATIONS
CONSTANT VOLTAGE OPERATION (CH1, CH2)
Line regulation
р 0.01%+3mV
Load regulation
р 0.01% + 3mV (rating currentр3A)
р 0.02% + 5mV (rating current >3A)
Ripple & noise
р 1mVrms 5Hz ~ 1MHz
Recovery tTime
р 100mS (50% load change, minimum load
0.5A)
CONSTANT CURRENT OPERATION (CH1, CH2)
Line regulation
Load regulation
р 0.2% + 3mA
р 0.2% + 3mA
Ripple current
р 1mVrms 5Hz ~ 1MHz
5V FIXED OUTPUT
Regulation
Ripple & noise
Line regulation р5mV
Load regulation р10mV
р 3mArms
TRACKING OPERATION (CH1, CH2)
Tracking error
Series regulation
Load regulation
Ripple & noise
FIXED OUTPUT (CH3)
Voltage
Line regulation
Load regulation
Ripple & noise
Output current
р 0.5% + 10mV of CH1
р 0.01% + 5mV
р 300mV
р 2mVrms, 5Hz ~ 1MHz
5V
р 5mV
р 10mV
р 2mVrms
3A
METER
Digital
Accuracy
SAFETY
CE mark
INSULATION
Chassis and terminal
Chassis and AC cord
POWER SOURCE
Input voltage
DIMENSIONS & WEIGHT
Case
3 1/2 digits 0.5" LED display
±( 0.5% of rdg + 2 digits )
IEC/EN 61010-1
Yes
р DC 500V / 20MW
р DC 500V / 30MW
AC 100V/120V/220V ±10%, 230V(+10% ~ -
6%), 50/60Hz
255(W) x 145(H) x 265(D) mm
Approx 7kg
SELECTION TABLE
MODEL
NUMBER
GPS-3303
CH1 / CH2
CH3
0-30V / 0-3A 5V / 3A Max
TRACKING
SERIES V
60V / 3A
TRACKING
PARALLEL I
30V / 6A
538
Doc. No. PBC9 Rev.C 28-4-11