English
Language : 

GPR-M Datasheet, PDF (1/1 Pages) Powerbox – 1 8 0 WAT T L I N E A R
GPR-M Series
180 WATT LINEAR
FEATURES
• Single Output
• 0.01% High Regulation
• Constant Voltage and Constant Current Operation
• Internal Select for Continuous or Dynamic Load
• Low Ripple and Noise
• Overload and Reverse Polarity Protection
• 3 1/2 Digit 0.5" LED Display
SPECIFICATIONS
CONSTANT VOLTAGE OPERATION
Line regulation
Load regulation
Ripple & noise
Recovery tme
Output range
р 0.01% + 3mV
р 0.01% + 5mV (<10A)
р 0.02% + 5mV (>10A)
р 1mVrms (5Hz - 1MHz)
р 100ms (50% load change, minimum load
0.5A)
0 to rated voltage continuously adjustable
CONSTANT CURRENT OPERATION
Line regulation
р 0.1% + 3mV
Load regulation
Ripple current
р 0.2% + 3mA
р 3mA rms
Outut range
0 to rating current continuously adjustable
METER
Digital
Accuracy
INSULATION
Chassis and terminal
Chassis and AC cord
Safety
CE mark
POWER SOURCE
Input voltage
DIMENSIONS & WEIGHT
Case
3 1/2 digit 0.5" LED display
± ( 0.5% of rdg + 2 digits )
20MΩ or above DC 500V
30MΩ or above DC 500V
IEC/EN61010-1
Yes
AC 100V/120V/220V/240V±10%, 50/60Hz
255(W) x 145(H) x 335(D)mm
Approx 11.5kg
SELECTION TABLE
MODEL
NUMBER
GPR-1810HD
GPR-3060D
GPR-6030D
OUTPUT VOLTAGE OUTPUT CURRENT OUTPUT POWER
0-18V
0-30V
0-60V
0-10A
0-6A
0-3A
180W
180W
180W
Doc. No. PBC9 Rev.C 28-4-11
Powering Progress – www.powerbox.com.au
535