English
Language : 

DRP Datasheet, PDF (1/2 Pages) Powerbox – Power will not de-rate for the entire input voltage range
DRP BN1PH Series
60 -480 WATTS AC / DC DIN RAIL
FEATURES
• 24VDC 60W - 480W
• 1Ph AC/DC Power Supply
• DIN Rail Mountable
• Power will not de-rate for the entire input voltage range
• Power Boost of 150% for 3 seconds
• Conformal coating on PCBAs
• To protect against common dust and chemical pollutants
• Operating Temp -25C to 80C
• MTBF DRP60W & 120W > 800 000hrs
• MTBF DRP240W & 480W > 500 000hrs
• Overvoltage / Overcurrent / Over Temperature / Protection
SPECIFICATIONS
OUTPUT
Output Voltage
Output Voltage Range
Output Current
Indicator
Output Power
Line Regulation
Load Regulation
PARD (20MHz)
Hold-up Time
INPUT
Input Voltage Range
Input Frequency
Input Current
Efficiency at 100% Load
Leakage Current
PROTECTIONS
Overvoltage
Overload/Overcurrent
Over Temperature
Short Circuit
Degree of Protection
Protection against shock
Galvanic Isolation
RELIABILITY
MTBF
Expected Life Time
24Vdc, 48Vdc
24V - 28Vdc, 48V-56Vdc
See Selection Table
Green LED (DC OK)
60W - 480W, See Selection Table
< 0.5% typ. (@ 85-264Vac input, 100% load)
< 1% typ. (@ 85-264Vac input, 0-100% load)
< 200mVpp
> 20ms @ 115Vac & 230Vac
85–264VAC 120-375 VDC
47-63Hz
DRP60: <0.8A @ 230Vac
DRP120: < 1.2A @ 230Vac
DRP240: < 1.3A @ 230Vac
DRP480: <3A @ 230Vac
> 91.0% @ 115VAC >93.0% @ 230VAC
< 1mA @ 240VAC
32V, +/-10% SELV Ouput, Hiccup Mode, Non-
Latching (Auto-Recovery)
> 150% of rated load current, Hiccup Mode, Non-
Latching (Auto-Recovery)
< 80C Surrounding Air Temperature @ 100%
load, Non-Latching (Auto Recovery)
Hiccup Mode, Non-Latching (Auto-Recovery)
when the fault is removed)
IP20
Class 1 with PE (Primary Earth) connection
Input to Output: 4.0KVAC
Input to Ground: 1.5KVAC
Output to Ground: 1.5KVAC
DRP60W & DRP20W: 800,000 hrs as per Telcordia
SR-332 I/P: 115Vac, O/P: 100% load, Ta 25C
DRP240W & DRP480W: 500,000 hrs as per
Telcordia SR-332 I/P: 115Vac, O/P: 100% load, Ta
25C
10 years (230Vac 50% load @ 40C)
ENVIRONMENTAL
Operating Temperature -25°C to +80°C
Storage Temperature -25°C to +85°C
Power De-rating
> 50°C (2.5% / °C)
Operating Humidity < 95% RH (Non-Condensing)
Operating Altitude 2,500m
MECHANICAL
Case Cover
Aluminium
Dimensions / Weight
DRP60: 121 x 32 x 119.3mm, 0.33Kg
DRP120: 121 x 32 x 123.1mm, 0.72kg
DRP240: 121 x 85 x 124.1mm, 1.1kg
DRP480: 121 x 144 x 118.6mm, 1.37kg
Indicator
Green LED (DC OK)
Input Terminal
3 Pins (Rated 300V/30A)
Output Terminal
Input Wire
4 Pins (Rated 300V/30A)
DRP60: AWG 22-12
DRP120: AWG 20-12
DRP240: AWG 16-14
DRP480, AWG 18-10
Output Wire
DRP60: AWG 22-12
DRP120: AWG 20-12
DRP240: AWG 16-14
DRP480: AWG 18-10
Mounting Rail
TS35 DIN Rail in accordance with EN60715
IEC AC Input
See PBB1P Series for IEC Input option
Drip Hood Cover
See PBB1P Series for Drip Hood Cover option
STANDARDS
C-Tick
AS/NZS CISPR11 Group 1 Class A.
Electronic Equipment
Electrical Safety
Industrial Control
CE
Materials & Parts
EN50718 / IEC62103 in Power Installatioins
SIQ to EN60950-1, UL/cUL recognized to
UL60950-1, CSA C22.2 No. 60950-1, CB scheme
to IEC60950-1
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-
01, CSA to CSA C22.2 No. 107.1-01 (File No.
181564)
In conformance with EMC Directive 2004/108/EC
and Low Voltage Directive 2006/95/EC
RoHS Directive 2011/65/EU Compliant
1
Doc. No. DRP BN1PH Series Rev.A 16-9-15