English
Language : 

XR1648 Datasheet, PDF (2/2 Pages) Power-One – Xscend Rectifier
Xscend Rectifier Data Sheet
Input
Model
Input Voltage
Current (max.)
Soft Start
Harmonics
Surge Immunity
Fuse
Connection
EMC
Output
Model
Output Voltage
Power (max.)
Current (max.)
Efficiency
(at 40-90% load)
Tolerance
Transient
Response
Load Sharing
Ripple
Psophometric
Connection
EMC
XR1648
XR1424
100-240 VAC ±15% single phase
(44-66 Hz)
(180-85 VAC at derated output
power)
<10 A
<13 A/1 ms
>0.98 typical
EN 61000-4-5
12.5 A -line, 12.5 A -neutral
FCI power connector™
EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B
XR1648
45-57 VDC
1600 W
at >180 VAC
(50-57 VDC)
675 W
at 180-85 VAC
(50-57 VDC)
XR1424
22.5-28 VDC
1400 W
at >180 VAC
(25-28 VDC)
675 W
at 180-85 VAC
(25-28 VDC)
32 A
56 A
>93%
>90%
(93.5% typical) (91% typical)
Vout +/- 1.0%, constant voltage
regulation
+/- 5% at load variation
10-90% or 90-10%
<5% of nominal current
<100 mV p-p (BW. 30 MHz)
<2 mV, according to CCITT
norms
FCI power connector™
EN 61000-6-2, EN 61000-6-4
Mechanical
Dimensions
(WxHxD)
102.87 x 88.9 x 241.3 mm
(4.05 x 3.5 x 9.5 in)
Weight
2.3 kg (4.12 lb)
Cooling
Fan cooled, speed controlled, and alarmed
Insulation
Reinforced insulation, tested at:
4.25 kVDC primary-secondary
2.12 kVDC primary-ground
0.75 kVDC secondary-ground
Mounting
19 in/ 2U subrack up to 4 modules
23 in/ 2U subrack up to 5 modules
Other Technical Data
Safety
CSA C22-2 No. 950, UL 1950 and
IEC60950/ EN 60950
Protection
Short circuit proof, automatic current limiting,
selective shutdown of modules at excessive
output voltage. Thermal protection derates
the output power 65°C ambient temperature.
Shutdown at >75°C with automatic restart.
Shutdown is load dependant, at low load typ
85°C. Input overvoltage disconnection at
>275VAC with automatic reset at >260VAC.
Alarms
High output voltage/ shutdown, Low voltage/
module failure. Each alarm has an LED
indicator on the front panel.
Indications
Green LED
Power ON
Yellow LED
Current limit/ thermal
protection
Red LED
Module failure
Audible Noise
<60dBA
Operating
Temperature
-40 to +65 °C up to 2000 m
-40 to +55 °C above 2000 m
Storage
Temperature
-40 to +85 °C
Radiated EMC
EN 61000-6-2, EN 61000-6-3,
FCC Part 15, Class B
Environment
Storage:
Transport:
Operation:
Earthquake:
ETS 300 019-2-1
ETS 300 019-2-2
ETS 300 019-2-3
GR 63 Core Zone 4
*Average performance for a single module.
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on
the date manufactured. Specifications are subject to change without notice.
SEP 14, 2006
Page 2 of 2
www.power-one.com