English
Language : 

PMP5 Datasheet, PDF (2/2 Pages) Power-One – Rectifier Module
PMP 5
Rectifier Module
Input
Model
Input
Voltage
Current
(max.)
Soft Start
PMP 5.24
PMP 5.48
PMP
5.24-110
PMP
5.48-110
195-276V AC single
phase, (44-66Hz)
93,5-148,5V AC single
phase, (44-66Hz)
<2.9A
<5.8A
<8A peak max. 5ms
<16A peak max. 5ms
Harmonics
Surge
Immunity
Fuse
EN 610555
Power Factor >0.99 at 50-100% load
EN 61000-4-5
T 3,15A
T 6A
Connection IEC-320/C14
EMC
EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B
Output
Model
Output
Voltage
PMP 5.24
22.5-28
VDC
PMP 5.48
45-56
VDC
PMP
5.24-110
22.5-28
VDC
PMP
5.48-110
45-56
VDC
Power (max.) 448W
448W
448W
448W
Current
(max.)
Efficiency
Tolerance
Transient
Response
16A
8A
16A
8A
>87%
>89%
>85%
>87%
Vout +/- 1%
+/- 5% at load variation 10-90% or 90-10%,
recovery time 10ms
Load Sharing <5% of nominal current
Ripple
<100mV p-p (BW. 30MHz)
Psophometric <2mV, according to CCITT norms
Connection DIN 41612F
EMC
EN 61000-6-2, EN 61000-6-4
Note: All specifications are subject to change without notification.
Mechanical
Dimensions
Weight
62 x 129 x 232mm
(2.4 x 5.1 x 9.1in.)
1.5kg (3.3lbs.)
Cooling
Natural convection
Insulation
Reinforced insulation tested at:
4.25 kV DC primary-secondary,
2.12 kV DC primary-ground,
2.12 kV DC secondary ground
Enclosure
IP20
Mounting
In 19” subrack up to 6 modules
Other Technical Data
Safety
EN 60950
Protection
Short circuit proof, automatic
current limiting, selective
shutdown of modules at
excessive output voltage.
Green LED Power ON
Indications
Red LED
High output
voltage/ shutdown
Audible
Noise
Operating
Temperature
Storage
Temperature
Radiated EMC
Red LED
<35dBA
Low voltage/
module failure
-25 to +55°C
-40 to +85°C
EN 61000-6-2, EN 61000-6-3,
FCC Part 15, Class B
Environment
Storage:
Transport:
Operation:
ETS 300 019-2-1
ETS 300 019-2-2
ETS 300 019-2-3
11V0005-066 PMP 5 V3.0 RevD
www.power-one.com