English
Language : 

PCU10 Datasheet, PDF (2/2 Pages) Power-One – Controller Module
PCU10 Controller Module Data Sheet
Input
Voltage
18-72V DC
Current
<200 mA at 48V, <400 mA at 24V
Interface
Display
2x16 character LCD
Communications RS232 serial interface for remote
control from a PC with PowCom
software.
Indications
Green LED -
Yellow LED -
Red LED -
Power ON
System warning
System alarm
Controls
Four pushbutton controls allow
menu navigation
Alarms
Alarm History
Alarm Contacts
The last 40 events are saved and
include a time and date stamp.
Four potential free change over
alarm contacts. Two open collector
outputs for LVD.
Alarms
High DC Voltage
1*
Low DC Voltage
1*
Load/ Battery Disc.
1*
Battery Fuse Failure
1*
DC Fuse Failure
1*
Module Failure
2*
Urgent Module Failure
1*
Main AC Failure
3*
Battery Failure
4*
Symmetry Failure
4*
4*
High Temperature
2*
High Load
* All alarms are indicated using an LED and displayed in
the LCD. The numbers represent an example of alarm
routing: 1) Urgent alarm, 2) Service alarm,
3) Main AC failure, 4) Battery related failure
Alarms are configurable by changing the EPROM
Other Technical Data
Dimensions
(WxHxD)
62 x 262 x 232mm
(2.4 x 10.3 x 9.1in)
Weight
0.5kg (1.1 lb.)
Operating
Temperature
-25 to +55 °C
Storage
Temperature
-50 to +85 °C
Environment
Storage:
Transport:
Operation:
ETS 300 019-2-1
ETS 300 019-2-2
ETS 300 019-2-3
Battery Management
Battery
An optional feature that allows
Disconnection voltage disconnection of batteries.
Boost
Charging
Battery Test
Symmetry
Measurement
Temperature
Compensation
Charging
Load
Shedding
(PLD)
Manual time controlled or
automatic boost charging with
adjustable time and voltage levels.
Automatic or manual testing of
batteries up to four times per year.
Variables include: test duration, end
voltage, Ah, and allowable
symmetry variation.
Optional tool that measures
batteries for early detection of
thermal runaway. Allows for
separate measurements of up to
three parallel battery branches, each
divided into four blocks.
Allows continuous adjustment of
output voltage according to battery
temperature. Feature includes
adjustable compensation factor and
separate thresholds for alarms.
Optional feature that allows voltage
or time controlled disconnection of
non-essential load.
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on
the date manufactured. Specifications are subject to change without notice.
NOV 01, 2006
Page 2 of 2
www.power-one.com