English
Language : 

LOK4001-2RLD Datasheet, PDF (2/4 Pages) Power-One – 15, 30 and 50 Watt AC-DC Converters
DIN Rail Mountable
LOS, LOR, LOK 4000 Series
Protection
Input fuse
Input transient protection
Output
not user accessible
voltage depending resistor (VDR)
no-load, overload and short circuit proof
1.6 A, slow blow
Control
Status indication
LED output O.K.
Output voltage adjustment
R input - recitfier version
Output undervoltage monitoring D battery charger
90...110% Uo nom
typ. 80% Uoset
Safety
Approvals
Electric strength test voltage
Pollution degree
Degree of protection
EN 60950, UL 1950, CSA22.2 No. 950, UL 508 listed
input/protective earth
input/output
output/protective earth
in progress
1.5 kV AC
3 kV AC
1 kV AC
2
IP 20
EMC
Electrostatic discharge
Electromagnetic field
Electr. fast transients/bursts
Surge
Conducted disturbances
Electromagnetic emissions
IEC/EN 61000-4-2, level 2 (8 kV)
IEC/EN 61000-4-3, level 2 (3 V/m)
IEC/EN 61000-4-4, level 3 (2 kV)
IEC/EN 61000-4-5, level 3, line to prot. earth (2 kV)
IEC/EN 61000-4-5, level 2, line to line (1 kV)
IEC/EN 61000-4-6, level 2 (3 V)
CISPR 22/EN 55022, conducted
criterion B
criterion B
criterion B
criterion B
criterion B
criterion A
class B
Environmental
Operating ambient temperature Ui nom, Io nom, convection cooled
Operating case temperature TC Ui nom, Io nom
Storage temperature
non operational
Damp heat
IEC/EN 60068-2-3, 93%, 40°C
Vibration, sinusoidal
IEC/EN 60068-2-6, 10...60/60...2000 Hz
Shock
IEC/EN 60068-2-27
Bump
IEC/EN 60068-2-29
MTBF
MIL-HDBK-217F, 6B, 40°
–10...50 °C
–10...80 °C
–40...85 °C
21 days
0.15 mm/2 gn
11 ms/15 gn
11 ms/10 gn
1'600'000 h
Options
Built-in second fuse in the neutral
F
No fuse fitted
(operation from DC voltage)
F1
System connectors with screw terminals
K
www.power-one.com
Edition 5/07.2001
243