S8JX Datasheet, PDF (7/28 Pages) Omron Electronics LLC – Switch Mode Power Supply
S8JX
Input specification
100/200 V (Selected)
Item
Power ratings *1
300 W
600 W
Efficiency
82% min.
80% min.
Voltage *2
100 to 120 VAC (allowable range: 85 to 132 VAC)
200 to 240 VAC (allowable range: 170 to 264 VAC)
(Switchable)
Frequency *2
50/60 Hz (47 to 450 Hz)
Current *3
100 V input
200 V input
8 A max.
4.5 A max.
14 A max.
8 A max.
Input
Power factor
---
Harmonic current emissions
---
Leakage current *3
100 V input
200 V input
0.5 mA max.
1 mA max.
Inrush current (for a 100 V input
cold start at 25°C) *3 200 V input
25 A max.
50 A max.
30 A max.
60 A max.
Noise filter
Yes
Voltage adjustment range *5
−10% to 15% (with V. ADJ)
Ripple *3
2% (p-p) max.
Input variation influence
0.4% max.
Output *4 Load variation influence
0.8% max. (0 to 100% load, rated input voltage)
Temperature variation influence
0.05%/°C max.
Startup time
650 ms max.
500 ms max.
Hold time *3
20 ms min.
Overload protection *6
105% to 175% of rated load current,
voltage drop, intermittent, automatic reset
105% to 175% of rated load current, Inverted
L voltage drop, the circuit will be shut OFF
when the overload exceeds 5 s. *9
Additional Overvoltage protection *7
functions Overheat protection
Parallel operation
Yes
No
Yes (up to 5 units)
Yes *9
Yes *9
Series operation
Yes (For up to two Power Supplies; external diodes required.)
Protective circuit operation indicator
No
Yes (color: red)
Ambient operating temperature
Refer to the derating curve in Engineering Data on page 13 (with no icing or condensation).
Storage temperature
−25 to 65°C (with no icing or condensation)
Ambient operating humidity
25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 25 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 25 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 25 mA)
Insulation resistance
100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance
150 m/s2, 3 times each in ±X, ±Y, ±Z directions
Output indicator
Yes (Color: Green)
Conducted Emissions *3
Conforms to EN 55011 Group 1 Class A and based on FCC Class A
EMI
Radiated Emissions
Conforms to EN 55011 Group 1 Class A
Other
Electrostatic Discharge
Confirms to EN61000-4-2
Radiated Electromagnetic Field Confirms to EN61000-4-3
EMS
Electrical Fast Transient/Burst
Surge
Confirms to EN61000-4-4
Confirms to EN61000-4-5
Conducted Disturbance
Confirms to EN61000-4-6
Voltage Dips/Short Interruptions Confirms to EN61000-4-11
UL UR: UL 508 (Recognition), UL UR: UL 60950-1 (Recognition)
Approved standards *10
cUL Listed: CSA C22.2 No.107.1
cUR: CSA C22.2 No. 60950-1
EN/VDE: EN50178 (= VDE 0160), EN 60950-1 (= VDE 0805 Teil 1)
(Terminal block: Based on DIN 50274 (VDE 0660-514))
SEMI
SEMI F47-0200 (200-VAC input)
Weight *8
1,600 g max.
2,500 g max.
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not
start. Refer to Overload Protection on page 15.
*2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*3. Rated input voltage: 100 or 200 VAC at 100% load.
*4. Output characteristics: Specified at power supply output terminals.
*5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output
voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged.
*6. For details, refer to Overload Protection on page 15.
*7. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*8. The weight indicated is a for Front-mounting, Open-frame Power Supply.
*9. The protection-ON alarm indicator will light as soon as the output is interrupted. For resetting, turn OFF the input power, leave for more than
three minutes , and then turn it back ON again.
*10.The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).