Safety Precautions
■ Precautions for Correct Use
Please observe the following precautions to prevent failure to operate, malfunction, or undesirable effect on product performance.
G3TB
I/O classification by the color is as follows:
AC equipment
100 to 240 VAC
G3TB-IAZR02P
AC input module
Yellow
5 to 24 VDC
DC equipment
5 to 24 VAC
G3TB-IDZR02P
DC input module
White
5 to 24 VDC
AC equipment
100 to 240 VAC 3 A
G3TB-OA203PZ
G3TB-OA203PZM
G3TB-OA203PL
G3TB-OA203PLM
AC output module
Black
5 to 24 VDC
(4 to 24 VDC)
PLC or logic circuitry
G3TB-ODX03P
Red
DC equipment
4 to 60 VDC/
40 to 200 VAC 3 A
G3TB-ODX03PM
G3TB-OD201P*
G3TB-OD201PM*
*With 1.5-A output.
DC output module
5 to 24 VDC
(4 to 24 VDC)
When mounting more than one output module, make a distance of 5
mm minimum between adjacent SSRs. Up to 16-point, 3-A load
switching is possible
5 mm min.
Output module
Connection
With the SSR for DC switching, the load can be connected to either
positive or negative output terminal of the SSR.
Protective Component
Since the SSR does not incorporate an overvoltage absorption com-
ponent, be sure to connect an overvoltage absorption component
when using the SSR under an inductive load.
Solid State Relay G3TB 417