English
Language : 

G3PA24 Datasheet, PDF (6/18 Pages) Omron Electronics LLC – Extremely Thin Relays Integrated with Heat Sinks
3. Insert the cartridge into the opening of the G3PA so that side A
and side B are even.
Side A
Side B
4. Tighten the screws on both the corners with a tightening torque of
0.59 to 0.78 N•m.
5. Tighten the screws on both the sides with a tightening torque of
0.59 to 0.78 N•m.
6. Attach the terminal cover.
7. Switch on the power and check the G3PA to be sure it works
properly.
■ Linking Terminal Connection
• Connecting with linking terminal for G3PA-210B(L)-VD, -220B(L)-
VD, -240B(L)-VD and G3PA-420B-VD(-2), G3PA-430B-VD(-2).
SSR1
SSR2
SSR1
SSR2
• Connecting with linking terminal to “G32A-D” series short circuit
unit. (Order short circuit units seperately.)
SSR G32A Unit
SSR G32A Unit
1. When SSRs are close
mounted, loosen the
M3.5 Sems screw and
flip the linking terminal
down.
2. Insert the linking
terminal securely
into the center of
the screw and
tighten the screw.
1. When SSR are close
mounted, loosen the
M3.5 Sems screw on
the G32A and flip the
linking terminal down.
*
* The cover will not fit if
the terminal protrudes.
2. Insert the linking terminal
securely into the center
of the screw and tighten
the screw. Ensure that
the linking terminal does
not protrude.
Connect the terminal with power off.
Linking terminal
Refer to the instruction manual for
the G32A-A Power Device Cartridge
to replace the G3PA's triac part.
Linking terminal
G3PA-420B-VD
Linking
terminal
Linking
terminal
When the temperature indicator has turned from pink to red, the G32-A-A Power Device Cartridge Use the terminal cover to prevent accidents
may have malfunctioned, in which case the cartridge must be replaced with a new one.
due to electric shock.
442
Solid State Relays G3PA