English
Language : 

61F-GP-NX Datasheet, PDF (5/15 Pages) Omron Electronics LLC – Floatless Level Switch
Liquid Level Indication
(Connection Example)
Connections
Commercial Voltage
RST
MCCB
Lower limit
61F-GP-N
8765
U
4
0V
24 V
Control
circuit
U
Power
8V
supply
U
3
9
10 11 1 2
Liquid Level Indication
Intermediate
61F-GP-N
87 65
U
4
0V
24 V
Control
circuit
U
Power
8V
supply
U
3
9
10 11 1 2
61F-GP-N@
Compact, Plug-in Type
61F-GP-N
Dimensions:
page 14
Upper limit
61F-GP-N
87 65
U
4
0V
24 V
Control
circuit
U
Power
8V
supply
U
3
9
10 11 1 2
(See note.)
Water supply
source
M
P
Water
tank
PS-4S
E1
E2
E3
E4
Upper limit
Intermediate
Lower limit
Note: The power supply phases (terminals 3 to 9) can be matched to use the same ground for the
common Electrode (the longest Electrode, terminal 4).
Principles of Operation
• Terminals 6 and 7, and terminals 10 and 11 on the lower -limit 61F-GP-N are shorted when the water level reaches E3 (indicator ON).
• Terminals 6 and 7, and terminals 10 and 11 on the intermediate 61F-GP-N are shorted when the water level reaches E2 (indicator ON).
• Terminals 6 and 7, and terminals 10 and 11 on the upper-limit 61F-GP-N are shorted when the water level reaches E1 (indicator ON).
5