English
Language : 

G3NAD210BDC524 Datasheet, PDF (4/18 Pages) Omron Electronics LLC – Solid State Relays G3NA
Specifications
G3NA
■ Ratings
Input (at an Ambient Temperature of 25°C)
Model
G3NA-2@@B
G3NA-4@@B
G3NA-D210B
G3NA-275B-UTU(-2)
G3NA-290B-UTU(-2)
G3NA-475B-UTU(-2)
G3NA-490B-UTU(-2)
Rated voltage
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
Operating
voltage
4 to 32 VDC
75 to 132 VAC
150 to 264 VAC
4 to 32 VDC
75 to 264 VAC
4 to 32 VDC
75 to 264 VAC
4 to 32 VDC
75 to 264 VAC
Impedance
(See note 1.)
Voltage level
Must operate voltage
Must release voltage
7 mA max. (See note 2.) 4 VDC max.
1 VDC min.
36 kΩ±20% (See note 4.) 75 VAC max. (See note 3.) 20 VAC min. (See note 3.)
72 kΩ±20%
150 VAC max. (See note 3.) 40 VAC min. (See note 3.)
(See note 5.)
5 mA max. (See note 2.) 4 VDC max.
1 VDC min.
72 kΩ±20%
75 VAC max.
20 VAC min.
15 mA max.
4 VDC max.
1 VDC min.
72 kΩ±20%
75 VAC max.
20 VAC min.
7 mA max.
4 VDC max.
1 VDC min.
72 kΩ±20%
75 VAC max.
20 VAC min.
Note: 1. The input impedance is measured at the maximum value of the rated supply voltage (for example, with the model rated at 100 to 120 VAC,
the input impedance is measured at 120 VAC).
2. With constant current input circuit system. The impedance for the G3NA-2@@B-UTU is 15 mA max.
3. Refer to Temperature Characteristics (for Must Operate Voltage and Must Release Voltage) in Engineering Data on page 7 for further
details.
4. The G3NA-240B(-UTU) is 72kΩ±20%.
5. The G3NA-240B(-UTU) is 20 VAC min.
Output
Model
G3NA-205B
G3NA-210B
G3NA-220B
G3NA-240B
G3NA-410B
G3NA-420B
G3NA-440B(-2)
G3NA-D210B
G3NA-275B-UTU(-2)
G3NA-290B-UTU(-2)
G3NA-475B-UTU(-2)
G3NA-490B-UTU(-2)
Rated load Load voltage
voltage
range
Load current (See note 1.)
With heat sink Without heat sink
(See note 2.)
Inrush current
VDRM, VCEO
(reference value)
24 to 240 VAC 19 to 264 VAC 0.1 to 5 A (at 40°C) 0.1 to 3 A (at 40°C) 60 A (60 Hz, 1 cycle) 600 V (VDRM)
0.1 to 10 A (at 40°C) 0.1 to 4 A (at 40°C) 150 A (60 Hz, 1 cycle)
0.1 to 20 A (at 40°C) 0.1 to 4 A (at 40°C) 220 A (60 Hz, 1 cycle)
0.1 to 40 A (at 40°C) 0.1 to 6 A (at 40°C) 440 A (60 Hz, 1 cycle)
200 to 480 VAC 180 to 528 VAC 0.2 to 10 A (at 40°C) 0.2 to 4 A (at 40°C) 150 A (60 Hz, 1 cycle) 1,200 V (VDRM)
0.2 to 20 A (at 40°C) 0.2 to 4 A (at 40°C) 220 A (60 Hz, 1 cycle)
0.2 to 40 A (at 40°C) 0.2 to 6 A (at 40°C) 440 A (60 Hz, 1 cycle)
5 to 200 VDC 4 to 220 VDC 0.1 to 10 A (at 40°C) 0.1 to 4 A (at 40°C) 20 A (10 ms)
400 V (VCEO)
24 to 240 VAC 19 to 264 VAC 1 to 75 A (at 40°C) 1 to 7 A (at 40°C) 800 A (60 Hz, 1 cycle) 600 V (VDRM)
1 to 90 A (at 40°C) 1 to 7 A (at 40°C) 1,000 A (60 Hz, 1 cycle)
200 to 480 VAC 180 to 528 VAC 1 to 75 A (at 40°C) 1 to 7 A (at 40°C) 800 A (60 Hz, 1 cycle) 1,200 V (VDRM)
1 to 90 A (at 40°C) 1 to 7 A (at 40°C) 1,000 A (60 Hz, 1 cycle)
Note: 1. The load current varies depending on the ambient temperature. Refer to Load Current vs. Ambient Temperature under Engineering Data
on page 6.
2. When an OMRON Heat Sink (refer to Options) or a heat sink of the specified size is used.
4