Engineering Data
■ Definition of Inrush Current, Start up Time and Hold Time
Input ON
Input OFF
AC input
voltage
Inrush current input application
AC input
current
90%
95%
Output
voltage
Start up time
■ Overload Protection
The Power supply is provided with an overload protection function
that protect the load and the power supply from possible damage by
over current. When the output current rises above between 105 to
130% (105 to 120% for the 40 A model) of the rated current, the pro-
tection function is triggered, decreasing the output voltage. When
output current falls within the rated range, the overload protection
function is automatically cleared.
■ De-rating Curve
P
Pmax
Hold up time
■ Overvoltage Protection
5 A and 10 A models
If output voltage exceed the rated voltage more than 25% (50% at
maximum) by some reason, then an auxiliary feedback circuit will
operate limiting the output voltage for safety.
20 A and 40 A models
If output voltage exceed the rated voltage more than 25% (50% at
maximum) by some reason, then the output voltage will be turned
OFF automatically for safety. To restart the S8VT, turn OFF the input
voltage, wait few minutes, then apply the input power again.
50%
60
70 °C
For UL and CSA the maximum temperature is 60°C
(70°C for the 20 A model)
Three-phase Input Switch Mode Power Supply S8VT
3