MKS-X Datasheet, PDF (3/12 Pages) Omron Electronics LLC – General Purpose Power Relays
■ Coil Ratings
Item Rated current (mA) Coil resistance Must operate
Rated voltage (V) 50 Hz 60 Hz
(Ω)
voltage (V)
Must release
voltage (V)
Max. voltage (V)
Power consumption
(VA, W)
AC 24
100
110
96.3
48.4
26.6
23.1
760
80% max. of rated 30% min. of rated 110% of rated
voltage
voltage at 60 Hz voltage
Approx. 2.3 VA
at 60 Hz
110
24.2
21.0
932
120
22.2
19.3
1,130
25% min. of rated
voltage at 50 Hz
Approx. 2.7 VA
at 50 Hz
200
13.3
11.6
3,160
220
12.1
10.5
3,550
230
11.5
10.0
4,250
240
11.0
9.6
4,480
DC 12
126
95
24
63.2
380
15% min. of rated
voltage
Approx. 1.5 W
48
32.0
1,500
110
13.6
8,060
220
6.8
32,200
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/-20% for AC rated current and
±15% for DC coil resistance.
2. Performance characteristic data are measured at a coil temperature of 23°C.
3. The Maximum Voltage is the highest voltage that can be applied to the coil temporarily, not continuously.
4. The rated current is approximately 5 mA higher for Models with Built-in Operation Indicators (DC operating coils).
■ Characteristics
Contact resistance (See note 2)
100 mΩ max.
Operate time (See note 3)
AC: 20 ms max.
DC: 30 ms max.
Release time (See note 3)
20 ms max.
Max. operating frequency Mechanical
18,000 operations/h
Electrical
Models for DC loads: 1,800 times/hour
Models for AC loads: 1,200 times/hour
Insulation resistance (See note 4)
100 MΩ min.
Dielectric strength
2,500 VAC 50/60 Hz for 1 min. between coil and contacts
2,500 VAC 50/60 Hz for 1 min. between contacts of different polarity
1,000 VAC 50/60 Hz for 1 min. between contacts of same polarity
Vibration resistance
Destruction:
Malfunction:
10 to 55 Hz, 1.0-mm double amplitude
10 to 55 Hz, 1.5-mm double amplitude
Shock resistance
Destruction:
Malfunction
1,000 m/s2 when relay is properly mounted into P7M-06P PCB socket
500m/s2 when relay is properly mounted into P7MF-06(-D) socket
100 m/s2
Life expectancy
Mechanical
1,000,000 operations min. (at 18,000 operations/hr)
Electrical (See note 5) 100,000 operations min. (at rated load and maximum switching frequency)
Minimum permissible load
(Reference value. See note 6)
10 mA at 24 VDC
Ambient operating temperature
−40°C to 60°C (with no icing or condensation)
Note: The range is −25°C to 60°C for models with built-in operation indicators.
Ambient operating humidity
5% to 85%
Weight
SPST-NO: Approx. 73 g, SPST-NO/SPST-NC: Approx. 82 g
Note: 1. The values given above are initial values.
2. The contact resistance was measured for 1 A at 5 VDC using the voltage drop method.
3. The operate time was measured with the rated voltage imposed and any contact bounce ignored at an ambient temperature of 23°C.
4. The insulation resistance was measured with a 500-VDC insulation resistance tester at the same places as those used for checking the
dielectric strength.
5. The electrical endurance was measured at an ambient temperature of 23°C.
6. P level: λ60=0.1 x 10-6/operations
General Purpose Power Relays MKS-X
3