English
Language : 

MK3P5-S-AC240 Datasheet, PDF (3/10 Pages) Omron Electronics LLC – General Purpose Relay MK
■ Characteristics
Contact resistance
Operate time
Release time
Operating frequency
Insulation resistance
Dielectric strength
Vibration
Shock
Ambient temperature
Humidity
Service Life
Weight
50 mΩ max.
AC: 20 ms max. DC: 30 ms max.
20 ms max.
Mechanical
18,000 operations/hour
Electrical
1,800 operations/hour (under rated load)
100 MΩ min. (at 500 VDC)
2,500 VAC, 50/60 Hz for 1 minute between coil and contacts
1,000 VAC, 50/60 Hz for 1 minute between contacts of same poles, between
terminals of the same polarity
2,500 VAC, 50/60 Hz for 1 minute between current-carrying parts, noncurrent-
carrying parts, and terminals of opposite polarity
Mechanical durability 10 to 55 Hz, 1.50 mm (0.06 in) double amplitude
Malfunction durability 10 to 55 Hz, 1.00 mm (0.04 in) double amplitude
Mechanical durability 1,000 m/s2 (approx. 100 G)
Malfunction durability 100 m/s2 (approx. 10 G)
Operation: -10° to 40°C (14° to 104°F)
35 to 85% RH
Mechanical
10 million operations min. (at operating frequency of 18,000 operations/hour)
Electrical
100,000 operations at rated load (at operating frequency of 1,800 operations/hour)
Approx. 85 g (3.0 oz)
Note: Data shown are of initial value.
■ Characteristic Data
Maximum switching capacity
MK2P-S
Electrical service life
MK2P-S, MK3P5-S
Rated operating voltage (V)
Rated operating current (A)
General Purpose Relay MK
3