K8AK Datasheet, PDF (26/88 Pages) Omron Electronics LLC – Measuring & Monitoring Relays | |||
|
◁ |
K8AK-VS
Connections
Wiring Diagram
âOvervoltage Operation Diagram
(Output Relay Drive Method: Normally Closed)
DIP switch setting: SW3 ON.
Power supply
voltage
Set value
Input
Hysteresis
(â5% to 50% of operating value)
Alarm indicator
Relay 11-14
Flashing
Lit
Relay 11-12
T: Operating time (0.1 to 30 s)
T
T1: Startup lock time (1 or 5 s)
T1
Note: The power ON lock prevents unnecessary alarms from being
generated during the instable period when the power is first
turned on. There is no relay output during timer operation.
âUndervoltage Operation Diagram
(Output Relay Drive Method: Normally Open)
DIP switch setting: SW3 OFF.
Power supply
voltage
Input
Set value
Alarm indicator
Relay 11-14
Flashing
Lit
Hysteresis
(5% to 50% of operating value)
Relay 11-12
T: Operating time (0.1 to 30 s)
T
T1: Power ON lock (1 or 5 s)
T1
Note: The power ON lock prevents unnecessary alarms from being
generated during the instable period when the power is first
turned on. There is no relay output during timer operation.
Single-phase power
A1
Power supply
voltage
A2
V1
Voltage input V2 C (COM)
V3
14
Signal output
12
11
Relay
signal
output
Load
Note: There is no polarity when a DC current input is used.
26
|
▷ |