CP1E-N40DR-A Datasheet, PDF (20/44 Pages) Omron Electronics LLC – The CP1E Package PLCs: Economical, Easy to use, and Efficient
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@
Allocating Built-in Output Terminals to Functions
Output terminals are allocated functions by setting parameters in the PLC Setup. Set the PLC Setup so that each terminal is used for only one function.
CPU Unit with
I/O points
Output terminal
block
Terminal Terminal
block label number
Other than those
shown right
Normal output
When a pulse output instruction
(SPED, ACC, PLS2, or ORG) is
executed
Setting in PLC Setup
Origin search setting on
Pulse Output 0/1 Tab Page
Fixed duty ratio pulse output
Pulse + direction
Use
When the PWM
instruction is executed
Variable duty ratio
pulse output
PWM output
00 Normal output 0
Pulse output 0 (pulse)
--
--
01 Normal output 1
Pulse output 1 (pulse)
10
02 Normal output 2
Pulse output 0 (direction)
--
PWM output 0
--
--
03 Normal output 3
Pulse output 1 (direction)
--
--
CIO 100
14
04 Normal output 4
05 Normal output 5
--
Pulse 0: Error counter reset
output
--
--
Pulse 1: Error counter reset
output
--
06 Normal output 6
--
20
07 Normal output 7
--
--
--
--
--
30
00 to 03 Normal output 8 to 11
--
CIO 101
40
04 to 07 Normal output 12 to 15
--
--
--
--
--
60
CIO 102 00 to 07 Normal output 16 to 23
--
--
--
These functions are supported only by N/NA-type CPU Units with transistor outputs.
20