English
Language : 

H3YN Datasheet, PDF (2/12 Pages) Omron Electronics LLC – Solid-state Timer (Miniature Timer with Multiple Time Ranges and Multiple Operating Modes)
Hold-down Clips
Model
Y92H-3
Y92H-4
Applicable Socket
PYF08A, PYF08A-N, PYF08A-E
PYF14A, PYF14A-N, PYF14A-E
PY08, PY08QN(2), PY08-02
PY14, PY14QN(2), PY14-02
Specifications
I Ratings
Time ranges
Item
Rated supply voltage
Pin type
Operating mode
Operating voltage range
Reset voltage
Power consumption
Control outputs
H3YN-2/-4/-4-Z
H3YN-21/-41/-41-Z
0.1 s to 10 min (1 s, 10 s, 1 min, or 10 min max. 0.1 min to 10 h (1 min, 10 min, 1 h, or 10 h max.
selectable)
selectable)
24, 100 to 120, 200 to 230 VAC (50/60 Hz)
12, 24, 48, 100 to 110, 125 VDC (see note 1)
Plug-in
ON-delay, interval, flicker OFF start, or flicker ON start (selectable with DIP switch)
85% to 110% of rated supply voltage (12 VDC: 90% to 110% of rated supply voltage)
(see note 2)
10% min. of rated supply voltage (see note 3)
100 to 120 VAC: Relay ON: approx. 1.8 VA (1.6 W) at 120 VAC, 60 Hz
Relay OFF: approx. 1 VA (0.6 W) at 120 VAC, 60 Hz
200 to 230 VAC: Relay ON: approx. 2.2 VA (1.8 W) at 230 VAC, 60 Hz
Relay OFF: approx. 1.5 VA (1.1 W) at 230 VAC, 60 Hz
24 VAC:
Relay ON: approx. 1.8 VA (1.4 W) at 24 VAC, 60 Hz
Relay OFF: approx. 0.3 VA (0.2 W) at 24 VAC, 60 Hz
12 VDC:
Relay ON: approx. 1.1 W at 12 VDC
Relay OFF: approx. 0.1 W at 12 VDC
24 VDC:
Relay ON: approx. 1.1 W at 24 VDC
Relay OFF: approx. 0.1 W at 24 VDC
48 VDC:
Relay ON: approx. 1.2 W at 48 VDC
Relay OFF: approx. 0.3 W at 48 VDC
100 to 110 VDC: Relay ON: approx. 1.6 W at 110 VDC
Relay OFF: approx. 0.4 W at 110 VDC
125 VDC:
Relay ON: approx. 1.6 W at 125 VDC
Relay OFF: approx. 0.4 W at 125 VDC
DPDT: 5 A at 250 VAC, resistive load (cosφ = 1)
4PDT: 3 A at 250 VAC, resistive load (cosφ = 1)
Note: 1. Single-phase, full-wave-rectified power supplies can be used.
2. When using the H3YN continuously in any place where the ambient temperature is in a range of 45°C to 50°C, supply 90% to 110% of
the rated supply voltages (supply 95% to 110% with 12 VDC type).
3. Set the reset voltage as follows to ensure proper resetting.
100 to 120 VAC: 10 VAC max.
200 to 230 VAC: 20 VAC max.
100 to 110 VDC: 10 VDC max.
B-88
Solid-state Timer H3YN