Probable cause of error
Troubleshooting methods
---
---
1
A momentary power failure has occurred in the Check that the output voltage is normal and no problems have occurred in other devices. No problems
input.
will be caused by continuing to use the Power Supply as is. To clear DC LOW1 (LED display and tran-
sistor output status), turn OFF the input power, and wait at least 60 s before turning ON the input Power
Supply again.
A momentary overload has occurred.
The load current has probably exceeded the rated current. We suggest reducing the connected load
or replace the Power Supply with one that has a higher capacity.
A momentary output voltage drop has occurred A large inrush current has probably flowed to the load side at startup. We suggest replacing the Power 2
at startup due to the capacity of the capacitive Supply with one that has a higher capacity.
factors on the load side or when the load is acti-
vated.
The output voltage has returned to normal volt- Turn OFF the input power, and wait at least 60 s before turning ON the input power again to clear the
age following a rapid drop caused by using the indicator status.
output voltage adjuster (V.ADJ).
Deterioration due to age (when the Power Sup- The internal parts of the Power Supply may have deteriorated due to age. We suggest replacing the
ply has been used for several years)
Power Supply. Also replace other Power Supplies that were purchased at the same time.
Overload (immediately following first use of the The load current has probably exceeded the rated current. Check the actual load current and Power
Power Supply or when increasing the load) Supply capacity. Continued use in overload status may damage the Power Supply.
3
The output voltage dropped to -10% or lower of Adjust the output voltage to the rated values using the output voltage adjuster (V.ADJ).
the rated voltage resulting from using the output
voltage adjuster (V.ADJ)
A sudden overload occurred and the Power
Supply remains in overload status.
An error has probably occurred in the load device. Turn OFF the input power, and check whether any
errors have occurred in the load device. Continued use in overload status may damage the Power Sup-
ply.
The output voltage remains low after a rapid Adjust the output voltage to the rated values using the output voltage adjuster (V.ADJ). To clear DC 4
voltage drop caused by using the output voltage LOW1 (LED display and transistor output status), turn OFF the input power, and wait at least 60 s be-
adjuster (V.ADJ).
fore turning ON the input power again.
The overload status continues to fluctuate fol- An error has probably occurred in the load device. Turn OFF the input power, and check whether any
lowing a sudden overload.
errors have occurred in the load device. Continued use in overload status may damage the Power Sup-
ply.
5
Deterioration due to age (after using the Power The internal parts of the Power Supply may have deteriorated due to age. Replace the Power Supply.
Supply for several years)
Also replace other Power Supplies that were purchased at the same time.
6
Overload (immediately following first use of the The load current has probably exceeded the rated current. Check the actual load current and Power
Power Supply or when increasing the load) Supply capacity. Continued use in overload status may damage the Power Supply.
Power Supply interrupted or damaged.
Check whether the input power is being applied correctly. If there is no output even though the input
power is applied correctly, the internal circuit is probably damaged.
Overvoltage protection operation
Turn OFF the input power, and wait at least 3 min before turning ON the input power again. If the same
status recurs, the internal circuit is probably damaged.
7
The short bar has fallen off, or the +S and -S ter- Check whether the +S and -S terminals are open. If so, the overvoltage protection function is activated.
minals are open.
Therefore, turn OFF the input power and wait at least three minutes before turning it ON again. (S8VM-
10024A@/P@ and S8VM-15024A@/P@ models only)
Output short-circuit
Remove the cause of the output short-circuit.
Intermittent operation due to overload (S8VM- The load current has probably exceeded the rated current. Check the actual load current and Power
01524A@/03024A@ only)
Supply capacity. Continued use in overload status may damage the Power Supply.
The Power Supply fails to start repeatedly due A large inrush current has probably flowed to the load side at startup. We suggest replacing the Power
to the capacity of the capacitive factors on the Supply with one that has a higher capacity.
load side.
8
The input turns ON and OFF repeatedly.
Check whether the Power Supply’s input voltage is being applied correctly.
The status repeatedly switches between normal An error has probably occurred in the load device. Turn OFF the input power, and check whether any
operation and output short-circuit.
errors have occurred in the load device.