E2EL-C1R5E1 Datasheet, PDF (12/16 Pages) Omron Electronics LLC – Cylindrical Proximity Sensor
E2EL
Item
AND
(serial
connection)
Examples
OR
(parallel
connection)
E2EL
Item
The Sensors connected together must satisfy the
following conditions:
iL + (N--1) x i = Upper--limit of control output of each
Sensor
VS -- N x VR = Load operating voltage
N=
iVV=SR
=
=
iL =
No. of Sensors
Residual voltage of each Sensor
Supply voltage
Current consumption of the Sensor
Load current
If the MY Relay, which operate at 24 VDC, is used as a
load for example, a maximum of two Proximity Sensors
can be connected to the load.
The number of Sensors connected in parallel varies with
the Proximity Sensor model.
Effects of Surrounding Metal
Shielded types
Shielded types allow direct installation on metal plates in an embedded manner without performance change. A minimum distance of 3sn
is required between the active surface and a metallic surface in front of the device. (Fig. 1).
For SUS shielded types the following minimum distances are required to avoid performance change (see Fig.2 and table below):
Shielded SUS Types
E2EL-- C2j-- DS
E2EL-- X2j-- DS
E2EL-- X4j-- DjS
E2EL-- X8j-- DjS
Free zone
0.5 mm
0.5 mm
1.0 mm
2.0 mm
3sn
Freezone
3sn
Fig.1: Shielded type (except SUS)
Fig.2: Shielded SUS type
Non-shielded types
Installation of non--shielded types in metal require the minimum distances according to Fig. 3.
3sn 2sn
d 3d
Fig.3: Non- shielded type