H3CR-AAC100240DC100125 Datasheet, PDF (10/22 Pages) Omron Electronics LLC – Solid-state Multi-functional Timers H3CR-A
H3CR-AP
H3CR-A
The start input of the H3CR-AP is voltage input. (Voltage imposition or open)
Voltage Inputs
No-contact Input
(Connection to PNP open
collector output sensor)
12 to 24 VDC
(sensor power supply)
Sensor
+ DC power
− supply
Timer
10 Power
supply (+)
6 Start
7 Input 0V
2 Power
supply
(−)
Operates with PNP transistor ON
No-contact Input
(Connection to NPN open
collector output sensor)
12 to 24 VDC
(sensor power supply)
Sensor
+ DC power
− supply
Timer
10 Power
supply (+)
6 Start
7 Input 0V
2
Power
supply (−)
Operates with NPN transistor ON
Contact Input
Operates with relay ON
Timer
10
Power
supply (+)
6 Start
7 Input 0V
2
Power
supply (−)
Note: The input circuit is isolated from the Note: Refer to the signal levels in the
power supply circuit. Thus, an NPN
following table and be aware of the
transistor can be connected.
minimum applicable load of the relay.
Note: Before making connections, refer to Safety Precautions (H3CR-@).
Voltage Input Signal Levels
No-contact 1. Transistor ON
input
Residual voltage: 1 V max.
The voltage between terminals 6 and 7 must be 10.8 VDC min.
2. Transistor OFF
Leakage current: 0.01 mA max.
The voltage between terminals 6 and 7 must be 1.2 VDC max.
Contact
input
Use contacts that can adequately switch 0.1 mA at each
operating voltage.
The voltage between terminals 6 and 7 with contacts ON or
OFF must satisfy the specified value.
Contacts ON
100-to-240-VAC and 100-to-125-VDC models: 85 to 264 VAC
or 85 to 137.5 VDC
24-to-48-VAC and 12-to-48-VDC models: 20.4 to 52.8 VAC or
10.8 to 52.8 VDC
Contacts OFF
100-to-240-VAC and 100-to-125-VDC models: 0 to 10 VAC or
0 to 10 VDC
24-to-48-VAC and 12-to-48-VDC models: 0 to 2.4 VAC or 0 to
1.2 VDC
10